background image

5

04/06/04  LIT-H200X-E02 H200.doc

SET POINT

50%

db

OUTPUT #1

d2

HUMIDIFICATION

35%

30%

45%

40%

pb

0%

HUMIDIFICATION

100%

OUTPUT #2

100%

0%

d2

OUTPUT #1

DEHUMIDIFICATION

65%

55%

60%

0%

70%

DEHUMIDIFICATION

100%

0%

100%

OUTPUT #2

CONTROL SCHEMATIC:                                                                                                                                              

TABLE 3: H200 PARAMETERS 

                                                                                                                                   

CODE

VALUES

DEFAULT
VALUE

DESCRIPTION

Db

0 to 40 % R.H.

25% R.H.

Dead Band between humidification  and dehumidification.

SL

30 to 100 % R.H.

85% R.H.

Supply Limitation: High humidity limit in the supply duct (H270 only)

d2

0 to 199 % (of proportional
band)

100%

Differential for output #2": Shift for output 2 relative to output 1

Pb

0 = 1.6 % R.H.
1 = 3.2 % R.H.
2 = 6.4 % R.H.
3 = 12.8 % R.H.
4 = 25.6 % R.H.

2= 6.4%
R.H.

Proportional Band

o1

0 = Humidification
1 = Dehumidification

"Output #1" Action for output no  1

o2

0 = Humidification
1 = Dehumidification

"Output #2" Action for output no  2

cc

2 = Without integral
3 = With integral

3

"Control Code"

t1

0 = On/off
1 = 8 minutes
2 = 1 second

"Time #1" Time period for output no  1

t2

0 = On/off
1 = 8 minutes
2 = 1 second

"Time #2" Time period for output no. 2

rA

0 = °C
1 = °F

1   DO NOT
CHANGE

"Range" Temperature Scale

Ca

±

 13 %

Calibration (  deviation  mode:  DO NOT MODIFY:  USE AUTOCAL PROCEDURE;
FOR H100 TRANSMITTER, USE THE ZERO POTENTIOMETER  ON THE
TRANSMITTER.

hA

0 à 127

"Hardware assembly"  Code related to thermostat model and entered at initial setup at
the factory.

it

1 to 99 = 1 TO 99  MINUTES

60

"Integral time"  Error integration time.

Lt

-40 à +40 °C (-40 à 105 °F)

-20 °F

"Lower temperature"  minimum outside temperature for setpoint reset (model H270 only)

Ht

-40 à +40 °C (-40 à 105 °F)

32 °F

"Higher temperature" maximum  outside temperature for setpoint reset  (model H270
only)

rE

1 à 99 % R.H.

20 % R.H.

"Reset” Minimum humidity value ( % HR ) (model H270 only)
Example: rE = 20%. Humidity setpoint will be reset from selected setpoint to 20%, from
Ht to Lt

pb = proportionnal band
d2 = differential between output #1 and #2
db = dead band between humidification
        and dehumidification

Fig.7: Control schematic

Summary of Contents for Micro-stat H200 Series

Page 1: ...page 5 for location Each humidistat is computer calibrated and factory programmed with default parameters All control parameters such as proportional band stage differential etc may be changed in the field with the H263 programming tool without having to remove the thermostat cover The H263 also doubles as a diagnostic tool and indicates the status of all the inputs and outputs and will reduce tro...

Page 2: ...y output and one relay dehumidify output Humidistat and sensor are duct mount Setpoint is user adjustable Resolution 0 5 for retransmit only See sensor specifications for dimensions of sensors Note the complete order code includes the sensor that will be shipped with the humidistat WIRING 2 ON OFF OUTPUTS Single transformer Fig 2 Wiring diagram with single transformer Multiple transformers Fig 3 W...

Page 3: ...o output 2 The humidity sensor is located in the return air duct Humidistat model number H200 69 13 10 Fig 6 Application example 6 COMMON N A INPUT MAIN SENSOR N A 10 Vdc 9 10 8 7 OUTPUT 1 TRANSMITTER 0 to 10 Vdc 0 to 5 Vdc OUTPUT 2 24 Vac 0 to 10 Vdc 4 5 3 24 Vac 2 1 FOR CONTROL HUMIDITY SENSOR RED BLACK WHITE DDC SYSTEM ELECTRONIC MOTOR or SCR or METER 6 COMMON N A N A INPUT MAIN SENSOR 10 Vdc 9...

Page 4: ...uct mounted humidistat This humidity sensor can be mounted directly onto the supply or return of the ventilation duct The H200 may be located on the wall with humidity sensing from the remote H71 sensor location H80 REMOTE WALL SENSOR H263 PROGRAMMING TOOL This humidity sensor can be wall mounted in any remote location The humidistat may be located on the duct or other location with humidity sensi...

Page 5: ...ol Code t1 0 On off 1 8 minutes 2 1 second Time 1 Time period for output no 1 t2 0 On off 1 8 minutes 2 1 second Time 2 Time period for output no 2 rA 0 C 1 F 1 DO NOT CHANGE Range Temperature Scale Ca 13 Calibration deviation mode DO NOT MODIFY USE AUTOCAL PROCEDURE FOR H100 TRANSMITTER USE THE ZERO POTENTIOMETER ON THE TRANSMITTER hA 0 à 127 Hardware assembly Code related to thermostat model and...

Page 6: ... 5 C to 50 C 32 F to 122 F Control 0 to 95 R H non condensing Sensor 0 to 100 R H see Note 1 Resolution 0 1 Repeatability 0 5 Accuracy and sensor interchangeability 2 R H from 0 to 100 R H Range 10 to 90 R H for 5 to 50 C 41 F to 122 F Temperature effect 0 05 F Outputs Isolated Triac 30 Vac at A max 0 to 5 VDC into 1KΩ resistance min 0 to 10 VDC into 2KΩ resistance min 0 5 VDC at 20 mA max for bot...