"Autocal" button

(Invisible)

1.00" [25mm]

1.275" [32mm]

Cover

1.275" [32mm]

2.8" [71mm]

2.8" [71mm]

3.275" [83mm]

Wiring from top

Security screw

Base

Wiring from back

2.0" [50.8mm]

3.77" [95.8mm]

Cover

0.9" [22.8mm]

1.60" [41mm]

4.5" [114mm]

AUTOCAL PROCEDURE                                             

1. Measure the room humidity near the Viconics

humidistat with an accurate hygrometer.

2.  Turn the humidistat set point dial to match the reading

of the hygrometer.

3.  Push and hold the autocal button for few seconds or

until the internal red light turns on.  Look through the
slots on the left side of the humidistat.

SENSOR FAILURE PROTECTION

                             

The sensor is the most sensitive part of the humidistat and
also the most exposed.  In the case of a sensor failure in
humidification mode, the H200 will automatically assume a
failsafe output of 0%.

SPECIFICATIONS                                                                                                                                                       

Operating Conditions: 5 °C to 50 °C ( 32 °F to 122 °F )

•Control:

0% to 95% R.H. non-condensing

•Sensor:

0% to 100% R.H. (see Note 1.)

Resolution:

± 0.1 %

Repeatability:

0.5 %

Accuracy and sensor interchangeability:

± 2 % R.H. from 0 to 100 % R.H.

Range:

10 % to 90 % R.H. for 5 to 50 °C
(41 °F to 122 °F )

Temperature effect:

0.05 % / °F

Outputs:

 Isolated Triac: 30 Vac at ½ A max.*
 0 to 5 VDC into 1K

 resistance min.

 0 to 10 VDC into 2K

 resistance min.

 0/5 VDC at 20 mA max.for both outputs

Power:

 24 VAC -15%, +10%; 50/60 Hz; 2 VA

Base & casing:  Off-white; self extinguishing

ABS plastic

*

Triac outputs can only switch AC loads. Use relays when

switching dc loads.

Note 1.

 Humidity sensor:  Solid state humidity sensor.

Suitable for normal, clean air.  Not to be used in
corrosive or harmful environment.

DIMENSIONS                                                                                                              

Note: Specifications and equipment are subject to change without prior notice.

TABLE 4: SENSOR
CHARACTERISTICS

Voltage between black and white
wire, terminals #6 and #7

HUMIDITY

SENSOR OUTPUT

0 %

1.05 V

5 %

1.19 V

10 %

1.34 V

15 %

1.48 V

20 %

1.63 V

25 %

1.77 V

30 %

1.92 V

35 %

2.06 V

40 %

2.20 V

45 %

2.35 V

50 %

2.49 V

55 %

2.64 V

60 %

2.78 V

65 %

2.93 V

70 %

3.07 V

75 %

3.21 V

80 %

3.36 V

85 %

3.50 V

90 %

3.65 V

95 %

3.79 V

100 %

3.94 V

Fig.8: Dimension drawing

Summary of Contents for Micro-stat H200 Series

Page 1: ...page 5 for location Each humidistat is computer calibrated and factory programmed with default parameters All control parameters such as proportional band stage differential etc may be changed in the field with the H263 programming tool without having to remove the thermostat cover The H263 also doubles as a diagnostic tool and indicates the status of all the inputs and outputs and will reduce tro...

Page 2: ...y output and one relay dehumidify output Humidistat and sensor are duct mount Setpoint is user adjustable Resolution 0 5 for retransmit only See sensor specifications for dimensions of sensors Note the complete order code includes the sensor that will be shipped with the humidistat WIRING 2 ON OFF OUTPUTS Single transformer Fig 2 Wiring diagram with single transformer Multiple transformers Fig 3 W...

Page 3: ...o output 2 The humidity sensor is located in the return air duct Humidistat model number H200 69 13 10 Fig 6 Application example 6 COMMON N A INPUT MAIN SENSOR N A 10 Vdc 9 10 8 7 OUTPUT 1 TRANSMITTER 0 to 10 Vdc 0 to 5 Vdc OUTPUT 2 24 Vac 0 to 10 Vdc 4 5 3 24 Vac 2 1 FOR CONTROL HUMIDITY SENSOR RED BLACK WHITE DDC SYSTEM ELECTRONIC MOTOR or SCR or METER 6 COMMON N A N A INPUT MAIN SENSOR 10 Vdc 9...

Page 4: ...uct mounted humidistat This humidity sensor can be mounted directly onto the supply or return of the ventilation duct The H200 may be located on the wall with humidity sensing from the remote H71 sensor location H80 REMOTE WALL SENSOR H263 PROGRAMMING TOOL This humidity sensor can be wall mounted in any remote location The humidistat may be located on the duct or other location with humidity sensi...

Page 5: ...ol Code t1 0 On off 1 8 minutes 2 1 second Time 1 Time period for output no 1 t2 0 On off 1 8 minutes 2 1 second Time 2 Time period for output no 2 rA 0 C 1 F 1 DO NOT CHANGE Range Temperature Scale Ca 13 Calibration deviation mode DO NOT MODIFY USE AUTOCAL PROCEDURE FOR H100 TRANSMITTER USE THE ZERO POTENTIOMETER ON THE TRANSMITTER hA 0 à 127 Hardware assembly Code related to thermostat model and...

Page 6: ... 5 C to 50 C 32 F to 122 F Control 0 to 95 R H non condensing Sensor 0 to 100 R H see Note 1 Resolution 0 1 Repeatability 0 5 Accuracy and sensor interchangeability 2 R H from 0 to 100 R H Range 10 to 90 R H for 5 to 50 C 41 F to 122 F Temperature effect 0 05 F Outputs Isolated Triac 30 Vac at A max 0 to 5 VDC into 1KΩ resistance min 0 to 10 VDC into 2KΩ resistance min 0 5 VDC at 20 mA max for bot...

Reviews: