028-5008-04 LIT-R851B -E04-EN 

Sep-19 

Innovative Control Solutions For Your Needs 

 

R851B STEP CONTROLLER 

WITH INTEGRATED VERNIER STAGE 

 

Analog 0 to 10 Vdc vernier stage 

 

8 step models 

 

Up to 16 stage total with a slave unit 

 

Test button 

 

 

DESCRIPTION 

The Viconics R851B series step controller is designed for cost 

effective, precise modulation of multi-stage control application. A 

common application is a multi-step electric boiler. 

 

An integrated vernier control output will give a precise and full 

modulation of the load from 0 to 100% of the total capacity. 

 

FEATURES AND BENEFITS 

Microcomputer-based design 

Accuracy and reliability 

Adjustable step-up and step- 

down time delay 

Tailor to exact application 

Adjustable Vernier ratio 

Simplifies design of 

proportional stage 

0-10 Vdc analog Vernier 

output 

Permits use of SCR power 

controller 

Up to 16 stages 

One product family can handle 

all applications 

Progressive or linear 

sequencing 

Increased flexibility 

Test button 

Quick troubleshooting 

 

MODELS AVAILABLE 

The R851B is available in 1 model 

 

R851B-8 

8 stage unit

 

If more than 8 stages are required, the R851B-8 can be used as a 

master unit with another R851B as a slave unit. Adding another unit 

can bring the total step number up to 16.

 

SPECIFICATIONS 

Operating conditions:  

0°C to 80°C ( 32°F to 176°F ) 
0 % to 95 % R.H. non-condensing 

Relay outputs: 

Pilot duty: 

-

 

24 - 120 Vac – 720 VA 

-

 

240 Vac – 690 VA 

Motor load: 

-

 

120 Vac – 1 HP 

-

 

240 Vac – 2 HP 

Vernier stage: 0 to 10 Vdc, 5 mA max. 
Input impedance: 0 to 10 Vdc into 10 K

Ω

 

minimum 

Power supply: 24 Vac -15%, +10% 50/60 Hz; up to18 VA 
Use a Class 1 ( properly fused ) or Class 2, CSA or UL recognized 

transformer for power supply & relay outputs. 
Agency Approval: cULus File # E212649

 

Specifications and equipment are subject to change without prior notice.

 

OVERRIDE TEST BUTTON 

The override test button can be used to by-pass the interstage delay and 

bring on all stage at one time. This simplifies the verification of configured 

maximum number of stage. A status led per step will come on for each of 

the configured stage.

 

INPUT SIGNAL 

The R851B has four 

INPUT 

dip switch 

(S1 to S4) 

to select the control signal input: They are compatible with industry standard signals. 

 

DIP SWITCH ADJUSTMENTS & WIRING CONTROL INPUT 

 

 

Input Signal Switch 

Switch #1 

Switch #2 

Switch #3 

Switch #4 

0 to 10 Vdc control signal ( 2 to 10 Vdc control range ) 

Off 

Off 

Off 

On 

4 to 20 mA control signal 

Off 

Off 

On 

Off 

If a slave unit is used, wire the control signal input to the master unit only 