Installation  

  Remove security screw on the bottom of repeater cover.  

  Open cover by pulling on the bottom edge of repeater. 

  Remove assembly and then remove wiring terminals from sticker. 

(Fig. 3) 

  Please note the FCC ID and IC label installed in the cover upon 

removal of cover of the wireless products. 

 
A) 

Installation ( wall or within suspended ceiling ):

 

1-  Swing open the repeater PCB to the left by pressing the PCB 

locking tabs. 

(Fig. 4)

 

2-  Pull 

cables 6” out of the wall.  

3-  Mounting surface must be flat and clean.  

4-  Insert cables in the central hole of the base.

 

 

5-  Align the base and mark the location of the two mounting holes 

on the wall. Install with proper side of base facing up. 

6-  Install anchors if required.

 

 

7-  Insert screws in mounting holes on each side of the base. 

(Fig. 4)

 

8-  Gently swing back the circuit board on the base and push on it 

until the tabs lock. 

10- Strip each wire 1/4 inches from end. 

11- Insert each wire according to wiring diagram.  

13- Gently push excess wiring back into hole 

(Fig. 5). 

14- Re-Install wiring terminals in correct location. 

(Fig. 5).

 

15- Reinstall the cover (top side first) and gently push extra wire 

length into the hole in the wall.

 

16- Install security screw. 

 

 

 

  Electronic controls are static sensitive devices.  

Discharge yourself properly before manipulation and 
installing the controller. 

 

  Short circuit or wrong wiring may permanently damage 

the controller or the equipment. 

 
 

  

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Location of PCB retaining tabs 

 
 
 
 

 

 
 
 
 
 
 
 
 

 

 

 

Re-install terminal blocks 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Repeater assembly  

(VRP5000W) 

 
 

 

 

 

 

Fig.3

 

Fig.5

 

Fig.4

 

Summary of Contents for VRP5000W1000W

Page 1: ...enable the remote controller s to re establish communication and act as bridge s to the main mesh The repeater s can be installed where most convenient such as a wall or in a suspended ceiling space i...

Page 2: ...er side of base facing up 6 Install anchors if required 7 Insert screws in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs...

Page 3: ...associated wireless controllers when possible 6 Always try to locate the VWG and JACE near on in line of sigh to as many wireless controllers as possible 7 Avoid metal brick walls or concrete obstruc...

Page 4: ...the cluster of devices distanced as recommended for the main network deployment Viconics Controller s Main Mesh Cluster VRP5000W1000W Repeater More than 1 can be used Remote Viconics Controller s Clu...

Page 5: ...se connectivity to wireless network and VWG is communicating with wireless repeater System Troubleshooting Recommendations 1 If a repeater is not detected by the VWG and JACE verify that the LED is bl...

Page 6: ...arameter value up Configuration parameters Default value Significance and adjustments Com Addr Repeater networking address Default value 254 Range is 0 to 254Valid range is 0 to 254 PAN ID Personal Ar...

Page 7: ...Canada Industry Canada ICES 003 Canada Agency Approvals all models FCC Compliant to CFR 47 Part 15 Subpart B Class A US CE EMC Directive 89 336 EEC Europe Union C Tick AS NZS CISPR 22 Compliant Austr...

Reviews: