10

Installer configuration parameter menu  

Configuration can be done through the network or locally at the thermostat. 

• 

To enter configuration, press and hold the middle button (°C/°F or Override) for 8 seconds 

• 

Press the same middle button repetitively to scroll between all the available parameters 

• 

Use the up and down key to change the parameter to the desired value. 

• 

To acknowledge and save the new value, press the middle button again. 

• 

The next listed parameter is now displayed 

 

Configuration interface 

Fan 

  Re-starts the configuration parameter list at the beginning 

°C/°F  
Override 

  Enters the configuration mode. Press and hold for 8 seconds 

Pressing repetitively will scroll all available parameters one by one 

Down 

  Adjust / rotate parameter value down 

Up 

  Adjust / rotate parameter value up 

 

 

 
User interface 

 

• 

Unoccupied mode Override 

An Override can be made on commercial models during an Unoccupied period. If the Override option is enabled in the 
lockout configuration pressing the middle override button will resume occupied setpoints for a time specified by 
parameter ToccTime 

 

• 

Keypad interface

 

System 

  Is used to toggle between the different system mode available as per sequence and menu selected

Pressing repetitively the button will toggle between all the available modes 
Available menus are dependent on selected sequence of operation 

Fan 

  Is used to toggle between the different fan mode available as per sequence and menu selected 

Pressing repetitively the button will toggle between all the available modes 
Available menus are dependent on selected sequence of operation and menu selected for Fan 

°C/°F 

Override 

 

 

 

Middle key is  

• 

°C / °F for Hotel models 

• 

Override for commercial models 

Down 

  Adjust the setpoints down 

 

In cooling mode only the cooling setpoint displayed, 

 

In heating mode only the heating setpoint displayed 

 

In auto mode, (See below) 

Up 

  Adjust the setpoints up 

 

In cooling mode only the cooling setpoint displayed, 

 

In heating mode only the heating setpoint displayed 

 

In auto mode, (See below) 

1.  Any setpoint change can be permanent or temporary based on configuration parameter (Setpoint Type) 
2.  Any setpoint written through the network, will be permanent and cancel any active temporary setpoints 

3. 

Lockouts of access to certain functions is made with configuration parameter (lockout)

 

 

• 

Occupied setpoint adjustments 

Cooling 
mode  

Heating 
mode  

Off mode 

Auto Mode 

• 

Setpoint presented to user is the setpoint from the last 
action taken by the thermostat or the one currently in use. 

• 

If the other setpoint is the one desired, then the MODE 
button is used to toggle between the current displayed one 
and the other. 

Cool XX.X °F or 
°C 

Heat XX.X °F or 
°C 

No access to 
setpoint 

Cool XX.X °F or °C or Heat XX.X °F or °C 

Toggle to ( Heat or Cool )with MODE button 

 

• 

Heat/Cool setpoint toggle with MODE button to be active only in AUTO mode. 

• 

If cooling, heating or off mode is active, function is disabled 

 

• 

Unoccupied and Stand-By setpoints adjustments 

Setting the stand-by and unoccupied setpoints is done through the network or through configuration setup only. 

Summary of Contents for VT7300A5000

Page 1: ...ls VT73xxX5000B is available on document ITG VT7300 PIR BAC Exx Information on the Wireless models VT73xxX5000W is available on documents ITG VWG 40 BAC Exx and LIT VWG 40 SETUP Exx Models available V...

Page 2: ...ements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door closed 3 RemOVR tempor...

Page 3: ...ntil the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correct location Fi...

Page 4: ...ose Heat BO 4 9 AO 2 Heat AO 2 10 BO 1 Open Cool BO 1 10 AO 1 Cool AO 1 11 BO 2 Close Cool BO 2 BO 2 Not used Blank Blank 12 BI 1 BI 1 BI 1 12 BI 1 BI 1 13 RS RS RS 13 RS RS 14 Scom Scom Scom 14 Scom...

Page 5: ...4 Vac Com 24 Vac Com 24 Vac Com 24 V Hot 24 V Com BO3 BO2 Heating Cooling valve 24 Vac Com OR 24 V Hot 24 V Com BO1 if N O BO2 if N C 24 V Hot 24 V Com BO3 if N O BO4 if N C BO1 if N O BO2 if N C 24 V...

Page 6: ...ing and or heating VT7300F5x00 x VT7305F5x00 x Analog actuator Mandatory Pipe no 2 pipes Fan Menu 0 L M H RA DA as per actuator If cooling only set SeqOpera 0 Cooling only If heating only set SeqOpera...

Page 7: ...me as per actuator SeqOpera 2 Cool Reheat UI3 COS 24 V Com 24 V Hot BO2 Close Fan L Fan M Fan H High Med Low 24 Vac fan relays Cooling Heating BO4 Close Normally Closed On Off Valve Cooling and Heatin...

Page 8: ...RS Scom RS C DI Aux Scom Scom RS Scom RS RS Wiring examples of 3 remote room sensors for averaging applications Temperature vs resistance chart for 10 Kohm NTC thermistor R25 C 10K 3 B25 85 C 3975K 1...

Page 9: ...f humidity display is not enabled Sys mode off Override RH display is conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled...

Page 10: ...d menu selected Pressing repetitively the button will toggle between all the available modes Available menus are dependent on selected sequence of operation and menu selected for Fan C F Override Midd...

Page 11: ...wireless network adapter is present If the thermostat is installed as a stand alone unit or with an Echelon adapter this parameter will not be used or displayed For BACnet MS TP models valid range to...

Page 12: ...ut no 2 configuration Default value None None No function will be associated with the input Door Dry Door contact Motion detector This configuration is only functional if binary input 1 is set to Moti...

Page 13: ...given of mode schedule and outdoor temperature On Scroll active Off Scroll not active AutoMode Enables Auto menu for Mode button Default value Off Enables Auto function for the mode button For sequen...

Page 14: ...idification based on central network requirements from the BAS front end On Dehumidification Authorized Off Dehumidification Not Authorized RH set Dehumidification setpoint Default is 50 RH Used only...

Page 15: ...y They will remain effective for the duration specified by ToccTime Setpoints will revert back to their default value after internal timer ToccTime expires To change setpoints permanently revert to No...

Page 16: ...models VT73xxC5x00 x only Default value 1 5 minutes Floating actuator timing Maximum stroke time of floating valve actuator Range is 0 5 to 9 0 minutes in 0 5 minutes increment cph On Off devices cyc...

Page 17: ...ions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada IC...

Reviews: