Schematic Wiring 

Settings 

4 pipe system cooling and heating: VT7300C5x00(x) & VT7305C5x00(x) On / Off N.C. actuators 

 

 

Mandatory 

• 

Pipe no = 4 pipes 

• 

CntrltTyp = On/Off 

• 

Fan Menu = 0 (L-M-H) 

• 

FL time = 

as per actuator 

• 

SeqOpera = 4 Cool/Heat 

4 pipe system cooling and heating: VT7300C5x00(x) & VT7305C5x00(x) Floating actuators 

 

 

Mandatory 

• 

Pipe no = 4 pipes 

• 

CntrltTyp = Floating 

• 

Fan Menu = 0 (L-M-H) 

• 

FL time = 

as per actuator 

• 

SeqOpera = 4 Cool/Heat 

 

4 pipe system cooling and heating: VT7300F5x00(x) & VT7305F5x00(x) Analog actuators 

 

 

Mandatory 

• 

Pipe no = 4 pipes 

• 

Fan Menu = 0 (L-M-H) 

• 

RA/DA = 

as per actuator 

• 

SeqOpera = 4 Cool/Heat 

2 pipe system cooling or heating with reheat: VT7300C5x00(x) & VT7305C5x00(x) Floating actuator 

 

 

Mandatory 

• 

Pipe no = 2 pipes 

• 

CntrltTyp = Floating 

• 

Fan Menu = 0 (L-M-H) 

• 

FL time = 

as per actuator 

• 

SeqOpera = 2 Cool/Reheat 

• 

UI3 = COS 

24 V~ Com

24 V~ Hot

BO2 Close

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

Cooling

Heating

BO4 Close

Normally Closed On/Off

Valve Cooling and Heating

Room Temperature
Control Thermostat

3 Speed fan

24 V~ Com

24 V~ Hot

BO1 Open

BO2 Close

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

Cooling

Heating

BO3 Open

BO4 Close

Modulating Floating

Valve Cooling and Heating

Room Temperature
Control Thermostat

3 Speed fan

24 V~ Com

24 V~ Hot

AO1

AO2

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

Cooling

Heating

0 t o  10

Vd c

0 t o  10

Vd c

Modulating Analog

Valve Cooling and Heating

Room Temperature
Control Thermostat

3 Speed fan

Optional supply water

temperature sensor

UI3 COS

24 V~ Com

24 V~ Hot

BO1 Open

BO2 Close

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

BO5

BO5

Modulating Floating

Valve Cooling and/or Heating

Room Temperature
Control Thermostat

3 Speed fan

Electric
Reheat

Summary of Contents for VT7300A5000

Page 1: ...ls VT73xxX5000B is available on document ITG VT7300 PIR BAC Exx Information on the Wireless models VT73xxX5000W is available on documents ITG VWG 40 BAC Exx and LIT VWG 40 SETUP Exx Models available V...

Page 2: ...ements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door closed 3 RemOVR tempor...

Page 3: ...ntil the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correct location Fi...

Page 4: ...ose Heat BO 4 9 AO 2 Heat AO 2 10 BO 1 Open Cool BO 1 10 AO 1 Cool AO 1 11 BO 2 Close Cool BO 2 BO 2 Not used Blank Blank 12 BI 1 BI 1 BI 1 12 BI 1 BI 1 13 RS RS RS 13 RS RS 14 Scom Scom Scom 14 Scom...

Page 5: ...4 Vac Com 24 Vac Com 24 Vac Com 24 V Hot 24 V Com BO3 BO2 Heating Cooling valve 24 Vac Com OR 24 V Hot 24 V Com BO1 if N O BO2 if N C 24 V Hot 24 V Com BO3 if N O BO4 if N C BO1 if N O BO2 if N C 24 V...

Page 6: ...ing and or heating VT7300F5x00 x VT7305F5x00 x Analog actuator Mandatory Pipe no 2 pipes Fan Menu 0 L M H RA DA as per actuator If cooling only set SeqOpera 0 Cooling only If heating only set SeqOpera...

Page 7: ...me as per actuator SeqOpera 2 Cool Reheat UI3 COS 24 V Com 24 V Hot BO2 Close Fan L Fan M Fan H High Med Low 24 Vac fan relays Cooling Heating BO4 Close Normally Closed On Off Valve Cooling and Heatin...

Page 8: ...RS Scom RS C DI Aux Scom Scom RS Scom RS RS Wiring examples of 3 remote room sensors for averaging applications Temperature vs resistance chart for 10 Kohm NTC thermistor R25 C 10K 3 B25 85 C 3975K 1...

Page 9: ...f humidity display is not enabled Sys mode off Override RH display is conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled...

Page 10: ...d menu selected Pressing repetitively the button will toggle between all the available modes Available menus are dependent on selected sequence of operation and menu selected for Fan C F Override Midd...

Page 11: ...wireless network adapter is present If the thermostat is installed as a stand alone unit or with an Echelon adapter this parameter will not be used or displayed For BACnet MS TP models valid range to...

Page 12: ...ut no 2 configuration Default value None None No function will be associated with the input Door Dry Door contact Motion detector This configuration is only functional if binary input 1 is set to Moti...

Page 13: ...given of mode schedule and outdoor temperature On Scroll active Off Scroll not active AutoMode Enables Auto menu for Mode button Default value Off Enables Auto function for the mode button For sequen...

Page 14: ...idification based on central network requirements from the BAS front end On Dehumidification Authorized Off Dehumidification Not Authorized RH set Dehumidification setpoint Default is 50 RH Used only...

Page 15: ...y They will remain effective for the duration specified by ToccTime Setpoints will revert back to their default value after internal timer ToccTime expires To change setpoints permanently revert to No...

Page 16: ...models VT73xxC5x00 x only Default value 1 5 minutes Floating actuator timing Maximum stroke time of floating valve actuator Range is 0 5 to 9 0 minutes in 0 5 minutes increment cph On Off devices cyc...

Page 17: ...ions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada IC...

Reviews: