background image

8

 

 

Remote sensor accessories 

 

 

 

Model no. 

Description 

S3010W1000 

Wall mounted temperature sensor 

S3020W1000 

Wall mounted temperature sensor with override button and 
occupancy status LED 

S2060A1000 

Averaging temperature sensor 

S2000D1000 

Duct mounted temperature sensor 

 

Remote mount temperature sensors use 10K type 2 NTC thermistors. 

 

Features:

 

• 

Each sensor can be configured for various averaging combinations 

FIG.8 – S3020W1000 WALL 

MOUNTED SENSOR

 

• 

Optional occupancy led 

• 

Optional override key 

 

Wiring example of single remote room sensor:

 

 

Wiring examples of 2 remote room sensors for averaging applications:

 

 

S3020W1000
Remote wiring 1 sensor

S2=On, S3=On

VT7300 Series
Thermostat

BO 5

BI 2

RS

Scom

Scom

RS

Scom

RS

C

DI

Aux

Scom

RS

Scom

RS

OR

S3010W1000
Remote wiring 1 sensor

S2=On, S3=On

24 Vac

Com

1

2

ON

Dip switch

setting for:

1 sensor

S2-1 = ON

S2-2 = ON

VT7300 Series
Thermostat

1 x S3010W1000 and 1 x S3020W1000
Remote wiring 2 sensors

S1=On, S2=Off

Scom

RS

Scom

RS

2 x S3020W1000
Remote wiring 2 sensors

S2=On, S3=Off

Scom

RS

Scom

RS

C

DI

Aux

VT7300 Series
Thermostat

BO 5

BI 2

RS

Scom

24 Vac

Com

Scom

RS

Scom

RS

C

DI

Aux

Scom

Scom

RS

Scom

RS

RS

Wiring examples of 3 remote room sensors for averaging applications:

 

 

 

 

Temperature vs resistance chart for 10 Kohm NTC thermistor 

(R

25°C 

= 10K

Ω

±3%, B

25/85°C

 = 3975K±1.5%)

 

 

ºC 

ºF 

Kohm 

 

ºC 

ºF 

Kohm

ºC

ºF

Kohm

ºC

ºF

Kohm

ºC

ºF 

Kohm 

-40 -40  324.3197   -20  -4 94.5149

0

32 32.1910

20

68 12.4601

40 104 5.3467 

-35 -31  234.4009   -15  5 71.2430

5

41 25.1119

25

77 10.0000

45 113 4.3881 

-30 -22  171.3474   -10  14 54.1988

10

50 19.7390

30

86

8.0694

50 122 3.6202 

-25 -13  126.6109    -5  23 41.5956

15

59 15.6286

35

95

6.5499

55 131 3.0016 

 

Notes for averaging applications: 

 

• 

S3010W1000 and S3020W1000 can be 
mixed matched.  

• 

S3010W1000 and S3020W1000 are to 
be wired in parallel. 

• 

Respect the dip switch setting in each 
remote sensor. 

1

2

ON

Dip switch 

setting for: 

2 sensors 

S2-1 = OFF

S2-2 = ON

 

1

2

ON

Dip switch

setting for:

3 sensors

S2-1 = OFF

S2-2 = OFF

2x S3010W1000 and 1 x S3020W1000
Remote wiring 3 sensors

S2=Off, S3=Off

Scom

RS

Scom

RS

Scom

RS

Scom

RS

VT7300 Series
Thermostat

BO 5

BI 2

RS

Scom

24 Vac

Com

Scom

RS

Scom

RS

C

DI

Aux

3x S3010W1000
Remote wiring 3 sensors

S2=Off, S3=Off

Scom

RS

Scom

RS

Scom

RS

Scom

RS

VT7300 Series
Thermostat

RS

Scom

Scom

RS

Scom

RS

BO 5

BI 2

24 Vac

Com

Aux

C

DI

2 x S3010W1000
Remote wiring 2 sensors

S2=On, S3=Off

Scom

RS

Scom

RS

VT7300 Series
Thermostat

RS

Scom

Scom

RS

Scom

RS

Summary of Contents for VT7300A5000

Page 1: ...ls VT73xxX5000B is available on document ITG VT7300 PIR BAC Exx Information on the Wireless models VT73xxX5000W is available on documents ITG VWG 40 BAC Exx and LIT VWG 40 SETUP Exx Models available V...

Page 2: ...ements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door closed 3 RemOVR tempor...

Page 3: ...ntil the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correct location Fi...

Page 4: ...ose Heat BO 4 9 AO 2 Heat AO 2 10 BO 1 Open Cool BO 1 10 AO 1 Cool AO 1 11 BO 2 Close Cool BO 2 BO 2 Not used Blank Blank 12 BI 1 BI 1 BI 1 12 BI 1 BI 1 13 RS RS RS 13 RS RS 14 Scom Scom Scom 14 Scom...

Page 5: ...4 Vac Com 24 Vac Com 24 Vac Com 24 V Hot 24 V Com BO3 BO2 Heating Cooling valve 24 Vac Com OR 24 V Hot 24 V Com BO1 if N O BO2 if N C 24 V Hot 24 V Com BO3 if N O BO4 if N C BO1 if N O BO2 if N C 24 V...

Page 6: ...ing and or heating VT7300F5x00 x VT7305F5x00 x Analog actuator Mandatory Pipe no 2 pipes Fan Menu 0 L M H RA DA as per actuator If cooling only set SeqOpera 0 Cooling only If heating only set SeqOpera...

Page 7: ...me as per actuator SeqOpera 2 Cool Reheat UI3 COS 24 V Com 24 V Hot BO2 Close Fan L Fan M Fan H High Med Low 24 Vac fan relays Cooling Heating BO4 Close Normally Closed On Off Valve Cooling and Heatin...

Page 8: ...RS Scom RS C DI Aux Scom Scom RS Scom RS RS Wiring examples of 3 remote room sensors for averaging applications Temperature vs resistance chart for 10 Kohm NTC thermistor R25 C 10K 3 B25 85 C 3975K 1...

Page 9: ...f humidity display is not enabled Sys mode off Override RH display is conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled...

Page 10: ...d menu selected Pressing repetitively the button will toggle between all the available modes Available menus are dependent on selected sequence of operation and menu selected for Fan C F Override Midd...

Page 11: ...wireless network adapter is present If the thermostat is installed as a stand alone unit or with an Echelon adapter this parameter will not be used or displayed For BACnet MS TP models valid range to...

Page 12: ...ut no 2 configuration Default value None None No function will be associated with the input Door Dry Door contact Motion detector This configuration is only functional if binary input 1 is set to Moti...

Page 13: ...given of mode schedule and outdoor temperature On Scroll active Off Scroll not active AutoMode Enables Auto menu for Mode button Default value Off Enables Auto function for the mode button For sequen...

Page 14: ...idification based on central network requirements from the BAS front end On Dehumidification Authorized Off Dehumidification Not Authorized RH set Dehumidification setpoint Default is 50 RH Used only...

Page 15: ...y They will remain effective for the duration specified by ToccTime Setpoints will revert back to their default value after internal timer ToccTime expires To change setpoints permanently revert to No...

Page 16: ...models VT73xxC5x00 x only Default value 1 5 minutes Floating actuator timing Maximum stroke time of floating valve actuator Range is 0 5 to 9 0 minutes in 0 5 minutes increment cph On Off devices cyc...

Page 17: ...ions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada IC...