22 | PIR Ready VT76x7 Series-Installation Guide
CONFIGURATION
PARAMETERS
DEFAULT VALUE
SIGNIFICANCE AND ADJUSTMENTS
PswrdSet
Configuration parameters
menu access password
Default value =
0
No password prompted
This parameter sets a password access to prevent
unauthorized access to the configuration menu parameters.
A default value of “0” will not prompt a password or lock the
access to the configuration menu.
Range is: 0 to 1000
Com Addr
Terminal Equipment
Terminal Equipment
Controller networking
address
Default value =
254
Range is: 0 to 254
Conditional parameter to
BACnet™ MS-TP models
(VT76xxX5x00B)
Conditional parameter to Wireless models (VT76xxX5x00W)
This parameter will only appear when a
BACnet™ or wireless
network adapter is present. If the Terminal Equipment Controller
is installed as a stand-alone (Network Ready) unit or with an
Echelon™ adapter, this parameter will not be used or displayed
-For
BACnet™ MS-TP models, the valid range to is from 1 to
127. Default value of 254 disables
BACnet™ communication for
the Terminal Equipment Controller.
For wireless models valid range is 0 to 254 with a maximum of
30 Terminal Equipment Controllers per VWG
PAN ID
Personal Area Network
Identification
Default value =
0
Range is: 0 to 1000
Conditional parameter to Wireless models
(VT76xxX5x00W)
This parameter will only appear when a wireless network
adapter is present. If the Terminal Equipment Controller is
installed as a stand-alone
(Network Ready)
unit or with a
BACnet™ or Echelon™ adapter, this parameter will not be
used or displayed
This parameter (Personal Area Network Identification) is
used to link specific Terminal Equipment Controllers to a
single specific Viconics wireless gateway ( VWG ) For every
Terminal Equipment Controller reporting to a gateway
( maximum of 30 Terminal Equipment Controllers per
gateway ), be sure you set the SAME PAN ID value both at
the gateway and the Terminal Equipment Controller(s).
The default value of 0 is NOT a valid PAN ID.