VD520 Series Inverter User Manual Parameter Description
- 135 -
F6-15
HDO1 Output Max
Frequency
0.01kHz~100.00kHz
50.00kHz
○
When selecting HDO1 terminals as pulse output, the function code is used to select the maximum
frequency value of the output pulse.
F6-16
AO1 Output Voltage
Lower Limit
0.00V~10.00V
0.00V
○
F6-17
Corresponding Setting
Value of AO1 Output
Voltage Lower Limit
0.0%~F6-19
0.0%
○
F6-18
AO1 Output Voltage
Upper Limit
0.00V~10.00V
10.00V
○
F6-19
Corresponding Setting
Value of AO1 Output
Voltage Upper Limit
F6-17~100.0%
100.0%
○
F6-20
AO1 Output Filter Time
0.00s~10.00s
0.00s
○
F6-21
AO2 Output Voltage
Lower Limit
0.00V~10.00V
0.00V
○
F6-22
Corresponding Setting
Value of AO2 Output
Voltage Lower Limit
0.0%~F6-24
0.0%
○
F6-23
AO2 Output Voltage
Upper Limit
0.00V~10.00V
10.00V
○
F6-24
Corresponding Setting
Value of AO2 Output
Voltage Upper Limit
F6-22~100.0%
100.0%
○
F6-25
AO2 Output Filter Time
0.00s~10.00s
0.00s
○
The function code used to set the relation of analog output voltage and its representing set value.
When AO1, AO2 output is the current output, 1mA current is equal to 0.5V voltage, so 20mA current
equal to10V.
When AO1, AO2 output is current output, it is suggested to add external resistor with less than 500
Ω.
F6-28
HDO1 Disconnect Delay
0.0s~3600.0s
0.0s
○
F6-29
T1 Disconnect Delay
0.0s~3600.0s
0.0s
○
F6-30
T2 Disconnect Delay
0.0s~3600.0s
0.0s
○
F6-31
DO1 Disconnect Delay
0.0s~3600.0s
0.0s
○
F6-32
DO5 Disconnect Delay
0.0s~3600.0s
0.0s
○
Set the closing delay time of output terminal HDO1, relay 1, relay 2, DO1 and DO5 from the state to
change to the actual output changes.