VD520 Series Inverter User Manual Parameter Description
- 157 -
Fb-21
Any Frequency Reaching
Detection Value 1
0.00Hz~max frequency
50.00Hz
○
Fb-22
Any Frequency Reaching
Detection Amplitude 1
0.0%~100.0% (max frequency)
0.0%
○
Fb-23
Any Frequency Reaching
Detection Value 2
0.00Hz~max frequency
50.00Hz
○
Fb-24
Any Frequency Reaching
Detection Amplitude 2
0.0%~100.0% (max frequency)
0.0%
○
When the output frequency of frequency converter, in the range of positive and nagetive detection
amplitude of the detection value at any time, muti-function DO output ON signal.
VD520 provides two sets of any frequency reaching detection parameters, set the frequency value
and frequency detection range respectively. The diagram below is a diagram of the function.
Running
frequency
Any frequency
reaching
Any frequency
reaching
detection DO or
relay
Time(t)
Frequency
detection range
Frequency
detection range
ON
OFF
OFF
OFF
ON
Fig 6-25 Schematic diagram of any frequency reaching detection
Fb-25
Zero Current Detection
Levels
0.0%~300.0%
100.0% corresponding rated motor
current
5.0%
○
Fb-26
Zero Current Detection
Delay Time
0.01s~600.00s
0.1s
○
When the output current of the inverter is less than or equal to zero current detection level, and the
duration is more than the zero current detection delay time, the inverter muti-function DO output ON
signal. Below is the zero current detection schematic diagram.