Mechanical and Electrical Installation VD520 Series Inverter User Manual
- 26 -
3.5.2 Standard Wiring Diagram for Three-phase and Lower than 15kW Inverter:
L1/R
L2/S
L3/T
P-
P+
T
R
S
PB
U
W
V
Brake unit
M
QF
DI4
T1/B
DI1
DI2
DI3
DI5
COM
AI2
GND
PE
T2/C
T1/C
5/10V
AI1
AO1
AO2
HDI1
T2/A
RS-485+
FWD/Stop
REV/Stop
T1/A
JOG
J14
+24V COM
J15
+10V
+5V
VR:1K~10K
DC0~10V
DC0~10V
DC0~20mA
DC0~10V
DC0~20mA
J5
V
A
J3
V
A
J4
V
A
RS-485-
DO1
+24V
HDO1
HDI
High pulse output
Collector output
Relay T1
Relay T2
RS-485
communication
terminal
Free stop
Fault reset
COM
VicRuns
Fig 3.5-2 Standard Wiring Diagram for three-phase and lower than 15kW Inverter
Precautions are as follows:
1) Terminal
◎
refers to Main circuit terminal, terminal
○
refers to control circuit terminal;
2) B which is followed the product model represents standard model built in brake unit
3)
Braking resistor’s selection is based on the user demand. refer to table 2-4;
4) Signal lines and power line must be separated alignments, if you want to control cables and power
cable cross, let them cross by 90 degree angle. It is best to choose shielded twisted-pair cabling for
analogue signal, the selection of power cable is shield three-core cable (The specification should
enlarge a file as much as the ordinary electric cables), or follow the inverter user manual