Function Parameter Table VD520 Series Inverter User Manual
- 54 -
F5-11
DI1 Terminal Mode
Selection 2
Effectively
Unit’s digit: HDI1
0: High level effective
1: Low level effective
Ten’s digit: reserved
Hundred’s digit: reserved
Thousand’s digit: reserved
0x0000
◎
F5-12
DI Filter Time
0.000s~1.000s
0.010s
○
F5-13
DI1 Close Delay
Time
0.0s~3600.0s
0.0s
◎
F5-14
DI2 Close Delay
Time
0.0s~3600.0s
0.0s
◎
F5-15
DI3 Close Delay
Time
0.0s~3600.0s
0.0s
◎
F5-16
DI1 Open Delay
Time
0.0s~3600.0s
0.0s
◎
F5-17
DI2 Open Delay
Time
0.0s~3600.0s
0.0s
◎
F5-18
DI3 Open Delay
Time
0.0s~3600.0s
0.0s
◎
F5-19
Terminal
UP/DOWN
Change Rate
0.001Hz/s~65.535Hz/s
1.000Hz/s
○
F5-20
AI Curve Selection
Unit’s digit: AI1 curve selection
1: Curve 1 (2 point, see F5-22~F5-26)
2: Curve 2 (2 point, see F5-27~F5-31)
3: Curve 3 (2 point, see F5-32~F5-36)
4: Curve 4 (4 point, see b2~00-b2-07)
5: Curve 5 (4 point, see b2-08~b2-15)
Ten’s digit: AI2 curve selection, same
as above
Hundred’s digit: reserved
0x321
○
F5-21
AI is Lower than
Min Input Set
Selection
Unit’s digit: AI1 is lower than min input
setting selection
0: Corresponding to the min input set
1: 0.0%
Ten’s digit: AI2 is lower than min input
setting selection, same as above
Hundred’s digit: reserved
0X000
○
F5-22
AI Curve 1 Min
Input
-10V~F5-24
0.00V
○