Function Parameter Table VD520 Series Inverter User Manual
- 84 -
A2-06
Asynchronous
Motor Stator
Resistance
0.001Ω~65.535Ω (Inverter
power≤55kW)
0.0001Ω~6.5535Ω (Inverter
power>55kW)
Tune
parameter
◎
A2-07
Asynchronous
Motor Rotor
Resistance
0.001Ω~65.535Ω (Inverter
power≤55kW)
0.0001Ω~6.5535Ω (Inverter
power>55kW)
Tune
parameter
◎
A2-08
Asynchronous
Motor Leakage
Inductive
Reactance
0.01mH~655.35mH (Inverter
power≤55kW)
0.001mH~65.535mH (Inverter
power>55kW)
Tune
parameter
◎
A2-09
Asynchronous
Motor
Interaction
Inductive
Reactance
0.1mH~6553.5mH (Inverter
power≤55kW)
0.01mH~655.35mH(Inverter
power>55kW)
Tune
parameter
◎
A2-10
Asynchronous
Motor No-load
Current
0.01A~ A2-
03 (Inverter power≤55kW)
0.1A~A2-03 (Inverter power>55kW)
Tune
parameter
◎
A2-26
Tune Parameter
0: No operation
1: Asynchronous motor static tuning
2: Asynchronous motor complete
tuning
0
◎
A3 Motor 2 Vector Control Parameters
Function
Code
Parameter
Name
Setting Range
Factory
Default
Value
Property
A3-00
Speed Loop
Proportion Gain
1
1~100
30
○
A3-01
Speed Loop
Integral Time 1
0.01s~10.00s
0.50s
○
A3-02
Switching
Frequency 1
0.00Hz~A6-05
5.00Hz
○
A3-03
Speed Loop
Proportion Gain
2
1~100
20
○
A3-04
Speed Loop
Integral Time 2
0.01s~10.00s
1.00s
○
A3-05
Switching
Frequency 2
A6-02~max frequency
10.00Hz
○
A3-06
Vector Control
Slip
Compensation
Gain
20%~200%
100%
○