7.
Pull the
“STOP”
knob on the control panel
to the out position.
8. Push the
“HYDRAULIC PUMP START”
button. Hydraulic oil will start flowing from
the tee through the bleeder tube and into
the tank.
8a. Place the switch on the control panel to the
“SET GUARD”
mode.
9. Depress the safety foot switch, hold it
down for 5 seconds, the release it for
5 seconds. Repeat this step until no air
bubbles can be seen through the clear
vinyl tube.
10. Push down (in) on the red
“STOP”
knob
on the control panel.
NOTICE
• To prevent oil from flowing out of the
tee while removing the bleeder tube and
installing the plug: Block the groove
diameter stop from moving down by
inserting a piece of wood between the
groove diameter stop and the top of the
hydraulic cylinder.
11. Remove the bleeder tube, and install the
plug into the tee.
DO NOT ALLOW AIR
TO GET BACK INTO THE TEE WHEN
INSTALLING THE PLUG (REFER TO
NOTICE BELOW).
TM-VE460_52
TM-VE460
OPERATING AND MAINTENANCE INSTRUCTIONS MANUAL
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.
REV_A