10.90
2870 Rev M Updated 04/2022 © 2022 Victaulic Company. All rights reserved.
4
4.0 DIMENSIONS
Sprinkler Barrel Length Selection
End seal
D
A
Cold space
Heated space
Wall or ceiling
of freezer
Insulation
1"/33.7 mm
Adapter
2" Hole Saw
Required for V36 and V40
2-¾" Hole Saw Required
for V33 (De-burr Hole on
Both Sides of the Ceiling
or Wall)
VicFlex™ Style AB6 bracket
assembly with integral seal
Plug
Temperature Maintained at 40°F/4.4°C Minimum
Ambient Temperature
Exposed to Discharge
End of Sprinkler
“D”
Freezer Ceiling
or Wall Thickness
“A”
Order Length
Down to 20°F
3 – 6"/76 – 152 mm
12"/305 mm
Down to -6.7°C
7 – 12"/178 – 305 mm
18"/457 mm
19°F to 0°F
3 – 6"/76 – 152 mm
18"/457 mm
-7.2°C to -17.8°C
7 – 12"/178 – 305 mm
24"/610 mm
-1°F to -20°F
3 – 6"/76 – 152 mm
24"/610 mm
-18.3°C to -28.9°C
7 – 12"/178 – 305 mm
30"/762 mm
-21°F to -30°F
3 – 6"/76 – 152 mm
24"/610 mm
-29.4°C to -34.4°C
7 – 12"/178 – 305 mm
30"/762 mm
-31°F to -40°F
3 – 6"/76 – 152 mm
24"/610 mm
-35.0°C to -40.0°C
7 – 12"/178 – 305 mm
30"/762 mm
Temperature maintained at 60°F/15.6°C
Ambient Temperature
Exposed to Discharge
End of Sprinkler
“D”
Freezer Ceiling
or Wall Thickness
“A”
Order Length
Down to 20°F
3 – 6"/76 – 152mm
12"/305 mm
Down to -6.7°C
7 – 12"/178 – 305mm
18"/457 mm
19°F to 0°F
3 – 6"/76 – 152mm
12"/305 mm
-7.2°C to -17.8°C
7 – 12"/178 – 305mm
18"/457 mm
-1°F to -20°F
3 – 6"/76 – 152mm
12"/305 mm
-18.3°C to -28.9°C
7 – 12"/178 – 305mm
18"/457 mm
-21°F to -30°F
3 – 6"/76 – 152mm
12"/305 mm
-29.4°C to -34.4°C
7 – 12"/178 – 305mm
18"/457 mm
-31°F to -40°F
3 – 6"/76 – 152mm
12"/305 mm
-35.0°C to -40.0°C
7 – 12"/178 – 305mm
18"/457 mm
Temperature maintained at 50°F/10°C
Ambient Temperature
Exposed to Discharge
End of Sprinkler
“D”
Freezer Ceiling
or Wall Thickness
“A”
Order Length
Down to 20°F
3 – 6"/76 – 152mm
12"/305 mm
Down to -6.7°C
7 – 12"/178 – 305mm
18"/457 mm
19°F to 0°F
3 – 6"/76 – 152mm
12"/305 mm
-7.2°C to -17.8°C
7 – 12"/178 – 305mm
18"/457 mm
-1°F to -20°F
3 – 6"/76 – 152mm
18"/457 mm
-18.3°C to -28.9°C
7 – 12"/178 – 305mm
18"/457 mm
-21°F to -30°F
3 – 6"/76 – 152mm
18"/457 mm
-29.4°C to -34.4°C
7 – 12"/178 – 305mm
24"/610 mm
-31°F to -40°F
3 – 6"/76 – 152mm
18"/457 mm
-35.0°C to -40.0°C
7 – 12"/178 – 305mm
24"/610 mm