background image

16

 

 

2. 

VERIFIC./EXTRACT

Shuts  down  due  to  the  revolution  sensor  of  the  smoke  extractor  motor  detecting  an 

anomaly.

 

- Check smoke extractor functionality (connection of the revolution sensor)

 

- Check smoke channel for dirt

3. 

STOP/FLAME

:

 Shuts  down  due  to  a  drop  in  smoke  temperature (intervenes if  the  thermocouple detects  a 

smoke temperature that is lower than that which is set, thereby interpreting it as a flame failure).

 

The flame may not go on for the following reasons:

 

- lack of pellets

 

- too many pellets in the combustion chamber have suffocated the flame

 

- the maximum thermostat / pressure switch / water safety thermostat has intervened to ‘stop’ the gear motor

4. 

BLOCK_FI/NO START

Shuts down due to incorrect smoke temperature during ignition (intervenes if the flame 

fails to appear within a maximum of 15 minutes, or if the ignition temperature is not reached). 

There are two possibilities:  
- 1. NO flame! Check: 
- Combustion chamber – position and proper assembly. 
- Correct work of the igniter. 
- The temperature in the room. If it’s lower than 3

о

С use fire lighter. 

- 2.There is flame but 

BLOCK_FI/NO Start

 is show on the display. 

The dealer must check: 
Proper work of the thermocouple. 
Set correct parameters for temperature ignition. 
5. 

Failure/Power

: Shuts down due to an electricity failure.

 

Check electricity connection and drops in voltage

6. 

FAULT /RC

:

 Shuts down due to a failure occurring in the thermocouple or it being disconnected

 

Verify connection of thermocouple to the control board. Verify functionality in a cold test

7. 

SMOKE

 O

С/HIGH

Shuts down due to excessive smoke temperature

 

An excessive smoke temperature may occur because of the following: unsuitable pellet type, anomaly in smoke 
extraction, blocked smoke channel, incorrect installation, gear motor ‘drift’

8. 

H2O TEMPALARM

Shuts down due to water temperature being higher than 90 °C.

 

An excessive temperature may occur because of the following:

 

- system too small: ask the DEALER to activate the ECO function

 

- blockage: clean the exchanger pipes, the combustion chamber and the smoke outlet

9. 

VERIFIC/AIR FLOW

:

 Shutdown due to loss of vacuum (occurs if the flow sensor detects insufficient 

combustion air flow). The air flow may be insufficient in the following cases:

 

- if the hatch is open or not properly sealed

 

- air suction or smoke expulsion problem

 

- combustion chamber clogged

 

- flow sensor dirty (clean with dry air)

 

- The vacuum alarm may even be activated during the start up phase

10. „

BATTERY CHECK

” : the stove is properly working but the error is show on the display. The battery of the 

circuit board needs change.  
11. The pellets does not enter in the combustion chamber. Few reasons are possible: 
- the feed screw is empty. Fill with pellets by pr and – buttons simultaneously.   
The pellets are blocked in the hopper.  
- use a vacuum cleaner to empty the pellet hopper. 
The gear motor is broken. (there will be error message). 
The feed screw safety thermostat ‘disconnects’ the electrical supply of the gear motor: 
- check that it has not overheated. Use a tester or a temporary bridge to verify. 
The water overheating safety thermostat ‘disconnects’ the electrical supply of the gear motor: 
- check that the stove contains water. 
- After having removed the protective cap, press the button on the back of the stove to reset 

In this cases you must contact the dealer before restarting

.

 

Note: all signals/warnings will remain shown until the control unit is used by pressing button 0/1. Do not use 
the stove until you solve the problem. It is very important for the dealer to know the exact message/signal

.  

12. The display/control unit is off. 
- check electric supply.  
- check the fuse. 
- check the connections of the flat cable.  
13. The water is not hot enough: 
- clean the heat exchanger. 

Summary of Contents for Vittoria B Series

Page 1: ...1 Instruction for installation and operation of pellet burning stove with integral water boiler VITTORIA...

Page 2: ...nciple of operation 7 7 Operation 8 8 Safety and detection devices 8 9 Components 8 10 Installation 9 11 Basic instructions for use 11 12 Instructions for use 12 13 Operating modes 12 14 Maintenance 1...

Page 3: ...can be damaged if it is ignited or used with no water in the system The stove is designed to heat water by means of automatic combustion of pellets wood with 6 mm diameter in the combustion chamber If...

Page 4: ...tly and safely The stove must be kept in a room where the temperature is above 0 C Use appropriate anti freeze additives for the water of the system Ensure that the temperature of the return water is...

Page 5: ...s are calculated on the basis of pellets with an heating value of at least 4300 kcal kg and heating loss of the roomof 33 Kcal m h It is also important to consider the position of the stove in the roo...

Page 6: ...has to be reset manually Tank safety thermostat Switches off when the temperature in the stove is too high It stops pellet loading which is causing the stove to shut down It has to be reset manually...

Page 7: ...ing the tank is thru the back of the lid at the rear of the top The fuel pellets is taken from the tank A and via an Archimedes screw powered by electric gear motor is transported to the combustion ch...

Page 8: ...mocouple It is located at the smoke exhaust to measure the temperature It is also controlling the ignition and if the temperature is too high or too low it triggers shut down sequence Stop Flame Hoppe...

Page 9: ...ations in the voltage above 10 can cause malfunction in the appliance unless the appropriate differential switch is installed The electrical system should be in accordance with all local regulations a...

Page 10: ...d into a chimney flue a vertical section of at least 1 5 m will be required complete with a wind guard The vertical duct can be internal or external If the smoke channel is outside it must be insulate...

Page 11: ...ring the filling bleed the pump manually and open the manual vent Picture 3 These actions must be carried subsequently periodically 11 Basic instructions for use Command board Picture 5 1 Button turn...

Page 12: ...date set 12 Instructions for use Feeling the feed screw When the tank for pellets is completely empty this means that the feed screw is also empty Before re igniting the stove you must fill it up fol...

Page 13: ...on the display if is pressed No Prog Prog No 1 one ignition and shutdown per day Prog No2 same as before Prog No3 same as before Use the button to show them in reverse order If you choose the first pr...

Page 14: ...not performed and at least once a season don t make a complete cleaning could cause to poor functionality Any problems resulting from lack of maintenance will immediately void the warranty Daily maint...

Page 15: ...own If the procedures for maintenance are not performed regularly the warranty will void If the stove is used very often it is recommended to clean the smoke channel once every 3 months Warning After...

Page 16: ...rift 8 H2O TEMPALARM Shuts down due to water temperature being higher than 90 C An excessive temperature may occur because of the following system too small ask the DEALER to activate the ECO function...

Page 17: ...stove produce hot air NO Most of the heat is transferred by the water Only small part of the heat is transferred to the room whre the stove is installed by means of radiant heat from the glass It is r...

Page 18: ...18...

Page 19: ...19...

Page 20: ...not kept damages caused during transport inappropriate made heating calculations and project for heating system and installation of the stove there have been made changes in the construction of the st...

Page 21: ...21 Victoria 05 Ltd 61A Anton Strashimirov Str 5100 Gorna Oryahovitsa Bulgaria phone 359 618 60282 fax 359 618 60200 e mail info v05 bg...

Reviews: