User Manual for ICHA Freezers
Victory
Electronic Controller Alarms
The alarm condition is always signaled by the alarm icon . To turn off the relative icon will continue flashing.
NOTE: If alarm exclusion times are in progress (ALA folder of the parameter table), the alarm is not signaled.
How to Acknowledge Alarms
Alarm
Code
Trigger
Automatic
Clearance
Outputs
Comments
"Hi"
Air temperature is higher
than "ALA->Hat• for "ALA-
>Htd"
User
configured
Bl ink "Hi" with the highest temperature; If
configured: cut in alarm relay, beep the buzzer
High temperature
alarm
"Lo"
Air temperature is lower than
"LAt" for "Ltd''
User
configured
Blink "Lo" with the lowest temperatu re. If
configured: cut in alarm relay, beep the buzzer
Low temperature
alarm
"Con"
Condenser temperature is too
high or too low
User
configured
Blink "Con". If configured: cut in alarm relay,
beep the buzzer
Condenser alarm
"dor"
Door open for more than
Always
Blink "dor". If configured: cut in alarm relay,
beep the buzzer
Door open alarm
"uHi"
Line voltage is higher than
"Cop->uHi"
Always
Blink "uHi". If configu red: cut in alarm relay,
beep the buzzer
High voltage alarm
"uLi"
Line voltage is higher than
"Cop->uLi"
Always
Blink "ulo". If configured: cut in alarm relay, beep
the buzzer.
Low voltage alarm
"LEA"
Compressor cont inuous
running for more than "ALA-
>LEA"
Always
Blink "LEA". If configured: cut in alarm relay,
beep the buzzer
Leakage alarm
"E01"
"S1" error
Always
Blink "SOl ". lf configured: cut in alarm relay,
beep the buzzer
"S1" sensor failure
(short or open)
"E02" "S1" error
Always
Blink "SO2". lf configured: cut in alarm relay,
beep the buzzer
"S2" sensor failure
(short or open)
"E03" "S1" error
Always
Blink "S03 ". lf configured: cut in alarm relay,
beep the buzzer
"S3" sensor failure
(short or open)
"E04" "S1" error
Always
Blink "SO4 ". lf configured: cut in alarm relay,
beep the buzzer
"S4" sensor failure
(short or open)