2. Features

The BatteryProtect offers a wide range of different features. These include:

• Protection of the battery against excessive discharge and can be used as a system on/off switch.

• 12/24V auto ranging. The BatteryProtect automatically detects system voltage one time only (can be re-triggered - see section

Programming table [11]

).

• A special setting for Lithium batteries. This feature allows external control from a BMS like the VE.Bus BMS or Lynx Smart

BMS. If the load disconnect output of a BMS is connected to the Remote H input and the signal becomes free-floating, the load
is immediately disconnected.

• Ultra-low current consumption of 1.5mA: This is important in case of Li-ion batteries, especially after low voltage shutdown.

• Over voltage protection: To prevent damage to sensitive loads due to over voltage. The load is disconnected whenever the DC

voltage exceeds 16.3V (for a 12V system) respectively 32.6V (for a 24V system).

• Ignition proof: No relays but MOSFET switches, and therefore no sparks.

• Delayed alarm output: The alarm output is activated if the battery voltage drops below the preset disconnect level fore more

than 12 seconds. Starting the engine will therefore not activate the alarm.

• Delayed load disconnect and delayed reconnect. Responding quickly within this delay, for example by reducing the load or

starting a generator or charger to charge the batteries, can prevent loads from being switched off.

For a full description of all features, please see the 

datasheets

.

BatteryProtect 12/24V

Page 2

Features

Summary of Contents for battery protect BP 100

Page 1: ...BatteryProtect 12 24V 12 24V 65A 12 24V 100A 12 24V 220A rev 00 08 2022 ENGLISH...

Page 2: ...3 3 4 BatteryProtect in a lithium system with external BMS and load disconnect output 7 3 3 5 Two BatteryProtects for load and charger control 8 3 3 6 BatteryProtect Alarm output wiring 8 4 Operation...

Page 3: ...remote on off port to protect from over voltage Compared to the Smart BatteryProtect the BatteryProtect must be programmed via the PROG pin to GND pin method The BatteryProtect is a uni directional d...

Page 4: ...nt in case of Li ion batteries especially after low voltage shutdown Over voltage protection To prevent damage to sensitive loads due to over voltage The load is disconnected whenever the DC voltage e...

Page 5: ...uit protection of the BP will be activated if you try to directly connect loads with capacitors for example inverters or inverter chargers on their DC inputs For that use case please use the BP to con...

Page 6: ...inverter charger via a BP you must use the BP to control the inverter or inverter charger via its remote port See example below Note that the image shown below is an example for all BatteryProtect mod...

Page 7: ...the load after 90 seconds automatically DC loads BatteryProtect in a simple system with wire loop between L and H input factory default The same example below This time the switch is wired between bat...

Page 8: ...s the BP via its remote terminal For this the BatteryProtect must be programmed to Li ion mode The dry contact is wired between the L and H connectors of the remote terminal If for example ATD opens i...

Page 9: ...when there is an actual low cell voltage and the BP will disconnect the load and remains off for 30 seconds even if it receives a restart signal H becomes high again within this period After this 30...

Page 10: ...of the BPs always follow the current flow from IN to OUT The positive terminal of the charger goes to the IN input of the BP DC loads BP 65 charge disconnect BP 65 load disconnect Two BatteryProtects...

Page 11: ...l disconnect the load after 90 seconds and the relay will disengage In case of over voltage the load will be disconnected immediately and the alarm output will remain inactive Overvoltage trip levels...

Page 12: ...re is a connection between the PROG pin and the GND pin the 7 segment display will first step through the shutdown and restart voltage combinations as indicated by the numbers 0 9 see the Programming...

Page 13: ...ehavior This section describes the behaviour of the BatteryProtect when it is controlled via the remote on off input and when a short circuit has been detected The BatteryProtect will connect the load...

Page 14: ...roof Load disconnect delay 90 seconds immidiate if triggered by a BMS Load reconnect delay 30 seconds Default thresholds Disengage 10 5 V or 21 V Engage 12 V or 24 V Operating temperature range Full l...

Page 15: ...re 1 Confirm that the load current draw does not exceed the BP current rating 2 Check for loose high resistance connections and ensure that appropriate gauge wiring is used in the installation 3 Do no...

Reviews: