M8 negative
connection
Cable seperators
Flip up the cable separator to reach the negative connections
Negative connection Lynx Distributor
6.2.4. Place Lynx Distributor fuses
Before placing fuses, first check if the bottom nuts of the middle row are tightened correctly to a use torque moment 10Nm.
Place all 4 fuses, even if not all 4 circuits are used. Placing dummy fuses in the unused circuits will prevent the red warning LED
to illuminate.
The second fuse connection has a wire with cable lug that is already connected to it. Leave this wire in place and place the fuse
on top of the red cable lug.
Lynx Distributor
Page 16
Installation