background image

 
 
 
 

 

 
 
 
 
 
 
 
 
 
Observe operating instructions and affix close 
within  sight  of  the  battery!  Work  on  batteries 
only under instructions of skilled personel! 
 
 
Smoking  prohibited! Do  not  expose  battery to 
open fame, glowing fire or sparks as explosion 
and fire hazard exists! 
 
 
When  working  on  batteries  wear  protective 
glasses and clothing! 
 
Explosion and fire hazard! Avoid short circuits! 
Caution!  Metal  parts  of  the  battery  cells  are 
always  live,  therefore  do  not  place  items  or 
tools on the battery! 
 
 
Electrolyte is strongly corrosive! 
 
 
Monoblock  batteries  /  cells  are  very  heavy!  
Ensure  secure  installation!  Only  use  suitable 
transport   equipment! 
 
 
Dangerous voltage! 
 
 
Acid splashes in the eyes or on the skin must 
be washed out or off with plenty of water. 
Then see a doctor immediately. Acid on 
clothing should be washed out with water! 
 
Safety requirements according to EN 50272-3 
 

 
 
 

 
1. 

Commissioning 

 
a) Filled and charged batteries 

Before commissioning all blocks must be  
inspected for mechanical damage, cells 
must be connected with the correct 
polarity and connectors firmly seated. 
The following torque apply for M10 screw 
connectors is: 

 
               

20 ± 1 Nm 

 
If necessary the terminal covers must be 
put  on. Check the electroiyte level in all 
cells. If necessary top up to maximum 
level with purified water as under DIN 
43530 Part 4. Before putting the battery 
in operation, plastic transport vent caps 
must be removed and replaced with 
ceramic cell plugs.  
With charger off and loads isolated 
connect battery to the direct current 
power supplies maintaining correct 
polarity (positive terminal to positive 
post).  
Switch on the charger and charge as 
under section 2.2. 

 

b) Dry charged (DC) batteries  

Instructions for the initial charging of a 
dry charged stationary OPzS and 
SOLAR (TOPzS) batteries: 

Unscrew the sealed vent plugs and 
fill the cells with pure dilute 
sulphuric acid, specific gravity 1,230 
0,01kg/1 read at 20 (68 F), up to 
about 25 mm below top of lid for 
SPgBG multi-block hard rubber 
containers and 50 mm below of lid 
for OPzS translucent containers or 
max level marked on the label. The 
temperature of the filling acid should 
be between 10°C and 25°C (50 - 77 
F). 

Insert the original plastic vent plug 
with Removed sealing foil on the top 
or place the special ceramic vent 
plug. 

Start charging for not less than 2 
and not more than 12 hours elapsed 
after the last cell has been filled with 
the acid. 

Apply the 0,5 x 110(5A/100Ah) 
current. 

Charge for 8 hours and then keep 
the battery on open circuit for 1-2 
hours. 

Continue the charging for a few 
hours, until the battery is fully 
charged, i.e. until constant voltage 
and constant specific gravity have 
been reached. The specific gravity 
of the acid in a fully charged celi is 
1,240 0,01 kg/I read at 20°C (68 F), 
If during the charging the 
temperature of the acid exceeds 
55°C (131 F) reduce the charging 
current by 50%. 

0,5 h after charging discharge the 
battery at 10 hour rate of current 
until the cell voltage drops to 
average value 1.80 Volts. Allowable 
minimum voltage of a single cell is 
1,70V.

 

 

Recharge the battery according to 
the operating instructions 2.2. 

24 hours after recharging adjust 
electrolyte level to the “max” mark 
on the label.  
Activation and test results must be 
kept as part of battery 
documentation. Non-compliance 
with this request renders the 
warranty null and void. 

 
 
 
 

2. 

Operation  

 
For the operation of stationary battery, 
installations EN 50272-2 apply  
 

2.1 Discharging  

 
Never allow the final discharge voltage of 
the battery to drop below that assigned 
for the discharge current. Charge 
immediately after discharge as well as 
partial discharge. Recommended DOD 
(Depth Of Discharge) for normal 
operating is up to 80% of CN. 
 

2.2 Charging  

 
All charging procedures with their limit 
values may be employed as stated 
below: 
DIN 41773 (lU characteristic)  
DIN 41774 (W characteristic) 
DIN 41776 (I characteristic).  
Depending on charger type and charging  
characteristic alternating currents flow 
through the battery superimposing onto 
the direct current. These alternating 
currents and the reaction of the loads 
lead to an additional warming of the 
battery and strain on the electrodes with 
possible resulting damage (see 2.5). 
Depending on the system at hand, 
charging may be carried out under the 
following modes: 
 

a) Stand-by parallel operation and 
floating operation. 

Here the load, direct current and battery 
are continuously connected in parallel. 
There by the charging voltage is at the 
same time the operating voltage of the 
system. With stand-by-parallel operation 
the direct current is at any time capable 
of supplying the maximum load current 
and the battery charging current. The 
battery only supplies current when the 
direct current source fails. The charge 
volt age should be set at 2,23 V +/-1% x 
number of cells measured at the 
battery’s terminals. To reduce the 
recharging time a charging stage can be 
applied in which the charging voltage is 
2,35 to 2,4 V x  
number of cells (stand-by parallel 
operation with recharging stage). 
Automatic changeover to the charging 
voltage of 2,23 V+/- 1% x number of cells 
follows after few hours on the voltage 
2,35-2,4 V x number of cells. With the 
floating operation the direct current 
source is not able to supply the 
maximum load current at all times.  
The load current intermit tently 
supersedes the nominal current of the 
direct current source. During this period 
the battery supplies power. It is not fully 
charged at all times.  Therefore, 
depending on the load the charge 
voltage must be set at 2.23 to 2.30 V x 
number of cells. 
 

b) Switch mode operation  

When charging the battery is separated 
from the load. Towards the end of the 
charging process the charge voltage of 
the battery is  2,6 - 2,75 V/cell. The 
charging process and parameters must 
be monitored (see Sections 2.4, 2.5 and 
2.6).  
 
On reaching a fully charged state the 
charging process must be stopped or 
switched to float charge as under Section 
2.3. 

 

OPERATING INSTRUCTIONS 

for stationary vented lead-acid 

OPzS SOLAR batteries 

 

Bat. Type: _________________________ 
Assembled by: _____________________ 
Date: _____________________________ 
Start-up by:________________________ 
Date:_____________________________ 

 

Non-compliance with operating 
instructions, repairs made with other 
than original parts, use of additives 
for the electrolyte (alleged “enhancing 
agents”) render the warranty null and 
void.

 

Reviews: