c) Battery operation

 (charge/discharge 

operation)  
Only the battery supplies the load. 
Hereby the charge voltage of the battery 
towards the end of the charging process 
is 2,6-2,75 V/cell. The charging process 
and parameters must be monitored (see 
Sections 2.4, 2.5 and 2.6).  When 
reaching a fully charged state the  
charging process must be switched off. 
The  battery can be switched to the load 
as necessary. 
 

2.3 Maintaining the full charge   
      (float charging) 

 

 

Devices complying with the stipulations 
under  DIN 41773 (lU characteristic) 
must be used. They are to be set so that 
the average cell voltage is 2,23V +/- 1% 
(2,25 V +/- 1% for UPS) cell at 20°C and 
the electrolyte density does not decrease 
over a protracted period  
(otherwise see 2.8). 
 

2.4 Equalizing charge  

Equalizing charges are required after  
exhaustive discharges and after 
inadequate charges; they can be carried 
out as follows: 

Up to 72 hours at constant voltage 
ofmax. 2.4 V/ celI, 

With the I or W characteristic as 
under 2.6. If during equalizing 
charging permitted load voltages 
are exceeded, appropriate 
measures must be taken,   e. g. 
disconnection of the load. If  
exceeding the maximum 
temperature of 55°C the charging 
must either be stopped, proceed 
with reduced current, or be switched 
to float charge to allow the 
temperature to drop. The equalizing 
charge is completed when the 
electrolyte densities no longer 
increases within a period of 2 hours. 

 

2.5 Alternating currents with periodic    
  deviations  
 

On recharging up to 2,4 V/cell as under  
operation modes a) to c) the actual value 
of the alternating current is occasionally 
permitted to reach max. 20 A per 100 Ah 
nominal capacity. Above 2,4 V/cells 10 A 
per 100 Ah nominal capacity may not be 
exceeded. In a fully charged state with a 
charge voltage  of 2,23 to 2,30 V/cell the 
actual value of the alternating current 
must not exceed 5 A per 100 Ah nominal 
capacity. 
 

2.6 Charging currents  

The charging currents are not limited up 
to 2,4 V/ celI. When exceeding the 
charging voltage of 2,4 V/cell, greater 
water decomposition occurs. The 
charging currents per 100 Ah nominal 
capacity shown in Table 1 must not be 
exceeded.  
 

Charging  
procedure 

Cell 
model 

Cell 
voltage 

I-charact. 

5,0 A 

2,6 

2,75 

W-charact. 

7,0 A 
3,5 A 

at 2,4 V 
at 2,65V 

 
 
 
 
 
 
 

 
 

2.7 Temperature  

 
The recommended operating 
temperature for Lead-acid batteries is 
10°C to 30°C. The technical data apply 
for the nominal  temperature 20°C. The 
ideal operating temperature is 20 +/- 5°C. 
Higher temperatures shorten the service 
life. Lower temperatures reduce the 
available capacity. The maximum  
temperature of 55°C must not be 
exceeded. 
 

2.8 Temperature-related charge 
voltage 

 
A temperature-related adjustment of the  
charge voltage within the operating 
temperature of 15°C to 25°C is not 
necessary. Should  the temperature 
range be lower than 15°C  and/or higher 
than 25°C a temperature related 
adjustment of the charge voltage should  
be made. The temperature correction 
factor is (-0.004 V/Cell per °K).  
Should the temperature constantly rise 
above 40°C then the factor is (-0.003 
V/Celi per °K). 
 

2.9 Electrolyte  

 
The electrolyte is diluted sulphuric acid. 
The nominal electrolyte density is based 
on 20°C and the nominal electrolyte level 
when fully charged with maximum 
dev/ - 0.01 kg/I. Higher 
temperatures reduce the electrolyte 
density; lower temperatures increase the 
electrolyte density. The associated 
correction factor is 0.0007 kg/I per °K. 
Example: electrolyte density of 1.23 kg/I 
at 35°C corresponds to a density of 1.24 
kg/I at 20°C or electrolyte density of 1.25 
kg/I at 5°C corresponds to a density of 
1.24 kg/I at 20°C. 
 

3. Battery maintenance and control  

 
The electrolyte level must be checked   
regularly. If it dropped to the lowest   
electrolyte level mark, purified water 
must be added as under DIN 43530 Part 
4, maximum  conductivity 30 

µ

S/cm. To 

avoid leakage currents keep the battery 
clean and dry (especially inter cell 
connections). Plastic battery 
components, in particular the vent caps, 
must only be cleaned with water that 
contains no additives. At least every 6 
months the following must be  
measured and recorded:  

Battery voltage  

Voltage of a few selected 
cells/mono block batteries  

Electrolyte density of a few selected 
cells/mono block batteries  

Electrolyte temperature of a few 
selected cells/mono block batteries. 

 
The following must be measured and  
recorded annually:  

Voltage of all cells/mono block 
batteries 

Electrolyte density of all cells/mono 
block batteries 

Electrolyte temperature of a few  
selected cells/mono block batteries 

Should the float charge voltage in 
one celi deviate more than + 0.1 V 
or - 0.05 V from the average value 
(see 2.3), equalizing charging 
should be done (see 2.4.). Annual 
visual checks: 

on bolted connectors (check that  
unsecured bolt connectors are 
firmly seated) 

 
 

on battery installation or 
arrangement 

 

on ventilation of battery room.

  

 

4. Tests  

Tests must be performed on fully charged 
batteries according to EN 60896-1.  
ln addition, special test instructions 
such as EN 50272-2 must be observed. 

 
5. Faults  

 
Should faults be detected in the battery 
or the charging device, customer 
services should be called in immediately. 
Measurement records under Section 3 
are necessary for fast fault detection and 
removal. 
 

6. Storage and taking out of operation  

 
Should cells/batteries be stored or taken 
out of operation for a longer period of 
time, they must be stored fully charged in 
a dry, frost-free room with max. 
temperature of 25°C. Direct sunlight or 
other heat sources must  
be avoided. To avoid damage the 
following charging methods can be 
chosen:  

a.

 Equalizing charges on a quarterly 

basis as under Section 2.4. In average, 
ambient temperatures of more than 30°C 
monthly equalizing charges may be 
necessary.  

b.

 Float charging as under Section 

2.3.above. 
 

7. Transport  

 
Batteries, wet, filled with acid require    
transport under demands of European   
Agreement concerning the international   
carriage of dangerous goods (ADR and 
RID). ADR special provision No. 598: 
New batteries are not subject to the 
requirements of ADR, when:  

they are secured in such a way that 
they can not slip, fall or be 
damaged;  

they are provided with carrying 
devices, unless they are suitably 
stacked, e.g. on pallets;  

there are no dangerous traces of 
alkalis or acids on the outside;  

they are protected against short 
circuits. 

 

8. Technical data  

 
The nominal voltage, the number of 
blocks, the nominal capacity (C10 = CN) 
and the battery type are obtained from 
the type plate. 
 
 
 