5. Configuration
•
Settings may only be changed by a qualified electrical engineer.
•
Read the instructions thoroughly before implementing changes.
•
During setting of the charger, the AC input must be removed.
5.1 Standard settings: ready for use
On delivery, the MultiPlus is set to standard factory values. In general, these settings
are suitable for single-unit operation.
Warning:
Possibly, the standard battery charging voltage is not suitable for
your batteries! Refer to the manufacturer's documentation, or to
your battery supplier!
Standard MultiPlus factory settings
Inverter frequency
50 Hz
Input frequency range
45 - 65 Hz
Input voltage range
180 - 265 VAC
Inverter voltage
230 VAC
Stand-alone / parallel / 3-phase
stand-alone
AES (Automatic Economy Switch)
off
Ground relay
on
Charger on/ off
on
Charging characteristics
four-stage adaptive with
BatterySafe mode
Charging current
75% of the maximum charging
current
Battery type
Victron Gel Deep Discharge (also
suitable for Victron AGM Deep
Discharge)
Automatic equalisation charging
off
Absorption voltage
14.4 / 28.8 / 57.6 V
Absorption time
up to 8 hours (depending on bulk
time)
Float voltage
13.8 / 27.6 / 55.2 V
Storage voltage
13.2V (not adjustable)
Repeated absorption time
1 hour
Absorption repeat interval
7 days
Bulk protection
on
AC input current limit
30A or 16A depending on model
(current limit for PowerControl and
PowerAssist functions)
UPS feature
on
Dynamic current limiter
off
WeakAC
off
BoostFactor
2
Multi-functional relay
alarm function
Summary of Contents for Phoenix MultiPlus 24/3000/70
Page 2: ......
Page 4: ......
Page 5: ......
Page 92: ...1 EN NL FR DE ES Appendix APPENDIX A Overview connections ...
Page 94: ...3 EN NL FR DE ES Appendix APPENDIX B Block diagram ...
Page 95: ...4 APPENDIX C Parallelconnection ...
Page 96: ...5 EN NL FR DE ES Appendix APPENDIX D Three phase connection ...
Page 99: ...8 APPENDIX G Dimensions ...
Page 100: ...9 EN NL FR DE ES Appendix ...