3.2. Warning when connecting inverters and inverters/chargers
Under no circumstances is it permitted to connect inverters or inverter/chargers to a SBP via their DC inputs,
a reverse current may flow that damages the SBP. In case you want to control an inverter or inverter/charger
via a SBP, you must use the SBP to control the inverter or inverter/charger via its remote port. See example
below. Note that the image shown below is an example for all BatteryProtect models including the smart
models.
DC loads
DC loads
Left image: Inverter DC input connected via a BatteryProtect - strictly forbidden
Right image: Inverter controlled by its remote port via BatteryProtect
Smart BatteryProtect 12/24V
Page 4
Installation and wiring examples