Trouble shooting guide 

 

The display does not show [--] when you power up :

  

Check the voltage 12 & - on the cpu. 
Disconnect everything except the supply into the CPU and check again. (If the fault goes 
away check all connections and wiring again). 
 

The reader head is only showing red in standby :

 

Check the LG1/2 connection from the cpu to the reader head for breaks. 
Check the voltage across LG1/2 & - (This should be 8V DC). Do this check at the CPU 
with both the Read head connected and disconnected. 
 

The reader head is only showing green in standby :

 

Check the LR1/2 connection from the cpu to the reader head for breaks. 
Check the voltage across LR1/2 & - (This should be 8V DC). Do this check at the CPU 
with both the Read head connected and disconnected. 

 
The LED’s on the read head are on but do not change state when a key is presented :

 

Check terminal RK1/2 for continuity and possible shorts to other wires. 
 

Reader head is going green when a key or Tag  is inserted but the door is not opening :

 

Check the relay is operating on the CPU. If the relay is operating : 
Check with a volt meter the voltage across the lock release when the relay has energized. 
If the correct voltage is there, replace the release. If not, check the cables from the 
release, back to the relay. 
 

The reader head is dead :

 

Check the - terminal to the reader head for continuity. 
Check the reader head connections for shorts. 
Check the CPU is powered up. 
 

The key has been programmed but the reader head is going red.

 

Check the key or Tag is programmed by using the read key mode on the CPU.  
Check in the programming that the door has not been switched off. 

VP100

Summary of Contents for VproX-100

Page 1: ...o access the programming menu Program up to 100 unique keys or Tags with door access options To modify the settings and parameters of a stored key Delete one or more keys or Tags Program each door relay time 1 to 99 seconds INITIALISATION When the installation has been completed carried out in accordance with the supplied wiring diagram the system can be powered up and programmed following the Vpr...

Page 2: ...umber of the 1st free location if available press enter to confirm or select another number by pressing the up arrow keys NOTE If when you press enter you hear a long beep that number is already taken and you must choose another number After pressing enter you may select using the up arrow keys which door the key has access to Default both doors on The doors are indicated by the decimal points on ...

Page 3: ...3 VP100 ...

Page 4: ...1 Normally closed contact Door one C1 Common contact Door one NO2 Normally open contact Door two NC2 Normally closed contact Door two C2 Common contact Door two LG1 Green LED s Door one LR1 Red LED s Door one RK1 Serial data Door one Negative Door one LG2 Green LED s Door two LR2 Red LED s Door two RK2 Serial data Door two Negative Door two Technical Specification Storage capacity 100 keys or Tags...

Page 5: ... CPU with both the Read head connected and disconnected The LED s on the read head are on but do not change state when a key is presented Check terminal RK1 2 for continuity and possible shorts to other wires Reader head is going green when a key or Tag is inserted but the door is not opening Check the relay is operating on the CPU If the relay is operating Check with a volt meter the voltage acro...

Page 6: ...6 VP100 ...

Page 7: ...7 VP100 ...

Reviews: