background image

14 of 20

Viega Multifunctional Thermostat User Guide

UG-HC 566441 1219 Multifunctional Thermostat (EN)

Technician Setup Steps

LCD will Show

Adjustment Options

Factory 

Default 

Settings

Gas Auxiliary for Heat Pump 

This option will turn the heat pump 

off 45 seconds after the auxiliary heat 

relay turns on.
For 2 stage heat applications, the first 

stage will turn off 45 seconds after the 

auxiliary stage turns on.
For 3 stage heat applications, the first 

and second stage will turn off 45 seconds 

after the auxiliary stage turns on.

For heat pump systems 

that are “dual fuel” 

(use a gas furnace for 

auxiliary stage heat) you 

can turn this feature 

on to turn off the heat 

pump when the auxiliary 

stage of heating has 

been called for.

OFF

Stages of Heat 

You can configure the thermostat to 

operate a 3 stage heat pump system.
2H 2C = 2 heat, 2 cool 

3H 2C = 3 heat, 2 cool
This feature only shows if Technician 

Setup step for heat pump is set to ON.

Use the + or - key to 

change between 2 heat 

and 3 heat
2 heat will use Y1 as 

first stage and W2 as 

auxiliary.
3 heat will use Y1 

as first stage, Y2 as 

second stage and W2 

as auxiliary.

2 Stages

Cooling Fan Delay 

The cooling fan delay setting will delay 

the fan from coming on in cool mode 

and keep running after the compressor 

shuts off for a short time to save 

energy in some systems.

You can select the 

Cooling Fan Delay from 

OFF, 15, 30, 60 or 90 

seconds.

OFF

IAQ Mode Cycle 

This feature will configure the fan to run 

a selected number of cycles “per hour”.
This mode can be enabled or disabled 

at anytime during normal operation, by 

selecting IAQ mode with the fan key.

Note: IAQ mode is a programmable/selectable 

mode will operate the fan 1-4 cycles per hour, 

1-45 minutes per cycle. Once programmed 

in tech setup, to enable this mode select IAQ 

with the fan key. Or you can disable the mode 

by selecting ON or AUTO with the fan key.

Select OFF, 1, 2, 3 or 4 

with the + or - keys.
This sets the number 

of cycles per hour that 

the IAQ fan mode will 

operate.

OFF

IAQ Mode Minutes 

This allows you to select the minimum 

number of minutes that the fan will run 

“per cycle”. The thermostat will keep 

track of fan run time from normal Heat 

and Cool operation. If additional fan 

runtime is needed the thermostat will run 

the fan to satisfy the IAQ mode minutes.

Select 1, 5, 10, 15, 20, 

30 or 45 minutes.
When IAQ fan mode is 

enabled, it will ensure 

the fan runs at least the 

selected number of minutes 

per IAQ mode cycle.

1

Summary of Contents for 15118

Page 1: ...o updates For the most current Viega technical literature please visit www viega us Pick an installation location that is easy for the user to access The temperature of the location should be representative of the building Installation Tips Applications Guide The Multifunctional Heat Cool Thermostat can be use for the following applications Gas or Oil Heat Electric Furnace Heat Pump No Aux or Emer...

Page 2: ...Subbase Attaching the Thermostat to the Subbase Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat then push gently until the thermostat snaps in place To insure a solid fit between the thermostat and the subbase Mount subbase to a flat wall or electrical box Use screws provided Drywall anchors should be flush with the wall Wires should be pushed into the wall A...

Page 3: ...n In systems with no emergency heat relay a jumper can be installed between E and W2 to turn thermostat into a single stage control Thermostat Wiring If you are replacing a thermostat make note of the terminal connections on the thermostat that is being replaced In some cases the wiring connections will not be color coded For example the green wire may not be connected to the G terminal Loosen the...

Page 4: ...ve energized in cooling Heat pump changeover valve energized in cooling G Fan relay Fan relay Fan relay W E First stage of heat First stage of emergency heat First stage of emergency heat Y First stage of cool First stage of heat cool First stage of heat cool Y2 Second stage of cool Second stage of cool Second stage of cool second stage of heat W2 Second stage of heat Auxiliary heat relay second s...

Page 5: ...tery power mode 3 3 8 3 3 3 3 8 3 3 8 8 3 3 O B 3 8 8 3 3 3 8 8 3 3 3 3 3 3 3 8 Typical 2H 2C System 1 Transformer Typical 2H 2C System 2 Transformers Typical 3H 2C Heat Pump System Typical Heat Only System with Fan Typical Cool Only System Typical Heat Only System with Fan HOT HOT HOT HOT Fan Relay Compressor Relay Heat Relay Compressor Relay 2 Auxillary Heat Change Over Valve Cool Change Over Va...

Page 6: ...inal from the thermostat to R terminal on the zone control Connect the W terminal from the thermostat to W terminal on the zone control for part number 15118 connect W E terminal from the thermostat to W terminal on the zone control Connect the C terminal from the thermostat to the C terminal on the zone control C terminal is optional but recommended when using with batteries Zone Control 18060 18...

Page 7: ... for part number 15118 connect W E terminal from the thermostat to W terminal on the zone control Connect the C terminal from the thermostat to the C terminal on the zone control C terminal is optional but recommended when using with batteries Viega Viega 0 0 8 3 8 3 8 3 8 3 N 3 3 8 5 3 3 0 8 8 3 3 0 8 3 3 0 8 MBDL 8IJUF FMMPX FMMPX 3FE 3FE FMMPX FMMPX 3FE 3FE Viega Viega Powerhead 15061 2 Wire 24...

Page 8: ...ga Thermostats to 2 Wire Powerheads Connecting Viega Thermostats to 4 Wire Powerheads 4 powerheads may be connected to each thermostat 4 powerheads may be connected to each thermostat C O B W E RH G Y Thermostat 15118 W2 Y2 RC Class II Transformer C R 120 V AC Power Supply N L Red Red Yellow Yellow Viega To T T boiler contact pump replay or other auxiliary device requiring contact closure Legend T...

Page 9: ...er day 42 the batteries must be replaced immediately to avoid freezing or overheating because the thermostat will shut the unit off until the battery is changed Thermostat Display 1 LCD Display 2 Glow in the dark light button 3 Set point buttons 4 6 Program buttons 7 Menu button 8 Fan button 9 System button 10 Button battery access door 11 Battery cover Days of the week and time Indicates the curr...

Page 10: ...re Calibration This feature allows the installer to change the calibration of the room temperature display For example if the thermostat reads 70 and you would like it to read 72 then select 2 You can adjust the room temperature display to read 4 F to 4 F above or below the factory calibrated reading 0 F Minimum Compressor On Time This feature allows the installer to select the minimum run time fo...

Page 11: ...fewer cycles The heating swing setting is adjustable from 0 2 F to 2 F For example A swing setting of 0 5 F will turn the heating on at approximately 0 5 F below the setpoint and turn the heating off at approximately 0 5 F above the setpoint 0 4 F Keypad Lockout Keypad lockout allows you to configure the thermostat so that none or some of the keys do not function Pick PA or FU PA partial keypad lo...

Page 12: ...ime period Wake Occupied Use the or key to turn on or off ON Program Options You can configure this thermostat to have a 7 day program a 5 1 1 program or nonprogrammable Use the or key to select 7d for 7 day 5d for 5 1 1 or 0d for nonprogrammable 5d Time Periods You can configure this thermostat to have 2 or 4 programmable time periods per day The 4 time periods are Wake Leave Return and Sleep 2C ...

Page 13: ...down for three seconds To remove the phone number from the display hold the light button for three seconds If selected on you will see the input screen after pressing next step Use the or key to select the desired number and the FAN or SYSTEM key to move from one character to another See note below operation OFF Beep When any key is pressed an audible beep will sound You can choose ON or OFF ON is...

Page 14: ...ry 2 Stages Cooling Fan Delay The cooling fan delay setting will delay the fan from coming on in cool mode and keep running after the compressor shuts off for a short time to save energy in some systems You can select the Cooling Fan Delay from OFF 15 30 60 or 90 seconds OFF IAQ Mode Cycle This feature will configure the fan to run a selected number of cycles per hour This mode can be enabled or d...

Page 15: ...nd the user to change the humidity pad Use the or key to select OFF 600 1000 1500 2000 These represent hours of heat operation OFF UV Lamp Reminder Will remind the user to change the UV light bulb Use the or key to select OFF 1 Year 2 Year OFF IAQ Cell Reminder Will remind the user to change the PHI Cell after 25 000 hrs Use the or key to select OFF 250 stands for 25 000 hours OFF Note Once a remi...

Page 16: ...UNOCC2 10 p m 62 F 17 C 78 F 26 C Saturday Wake OCC1 8 a m 70 F 21 C 75 F 24 C Leave UNOCC1 10 a m 62 F 17 C 83 F 28 C Return OCC2 6 p m 70 F 21 C 75 F 24 C Sleep UNOCC2 11 p m 62 F 17 C 78 F 26 C Sunday Wake OCC1 8 a m 70 F 21 C 75 F 24 C Leave UNOCC1 10 a m 62 F 17 C 83 F 28 C Return OCC2 6 p m 70 F 21 C 75 F 24 C Sleep UNOCC2 11 p m 62 F 17 C 78 F 26 C All our programmable thermostats are shipp...

Page 17: ...turday Occupied 8 a m 70 F 21 C 73 F 23 C Unoccupied 6 p m 64 F 18 C 80 F 27 C Sunday Occupied 8 a m 70 F 21 C 73 F 23 C Unoccupied 6 p m 64 F 18 C 80 F 27 C Day of the Week Programming Table Events Time Setpoint Temperature Heat Setpoint Temperature Cool Weekday Wake OCC1 Leave UNOCC1 Return OCC2 Sleep UNOCC2 Saturday Wake OCC1 Leave UNOCC1 Return OCC2 Sleep UNOCC2 Sunday Wake OCC1 Leave UNOCC1 R...

Page 18: ...ke Leave Return Sleep or Occupied 1 Unoccupied 1 Occupied 2 Unoccupied 2 To customize your 5 1 1 program schedule follow these steps Weekday 1 Select HEAT or COOL using the SYSTEM key You have to program heat and cool each separately 2 Press MENU 3 Press SET SCHED 4 Time is flashing Use the or key to make your time selection for the weekday WAKE OCC1 time period 5 Press NEXT 6 The setpoint tempera...

Page 19: ...Press SET SCHED 4 Time is flashing Use the or key to make your time selection for the weekday OCCUPIED time period 5 Press NEXT STEP 6 The setpoint temperature is flashing Use the or key to make your setpoint selection for the weekday OCCUPIED period 7 Press NEXT 8 Repeat steps 4 through 7 for weekday UNOCCUPIED time period Saturday 9 Repeat steps 4 through 7 for Saturday OCCUPIED time period and ...

Page 20: ...e display when your air filter needs changed FILT will be shown in the display after your system has run long enough to require an air filter change Resetting the filter change reminder When FILT reminder is displayed you should change your air filter and reset the reminder by holding down the third button from the left side of the thermostat for three seconds Auto Changeover If in Auto you have t...

Reviews: