2
©
Copyright 2010 Schneider Electric All Rights Reserved.
F-27027-5
SPECIFICATIONS
Inputs
Power Input:
20 to 32 Vac, 75 mA to 1.2 amps.
Outputs
Electrical:
Battery,
Setpoint backup (Energizer 357 or equivalent).
Mechanical:
Operating Differential,
Heating 1 or 2F degrees (0.6 or 1.1C degrees), Cooling 2F
degrees (1.1C degrees).
Setpoint Adjustment Range,
50 to 86
°
F (10 to 30
°
C).
Material,
Rigid vinyl.
Finish,
Off-white.
Environment
Temperature limits:
Shipping & Storage,
-40 to 125
°
F (-40 to 52
°
C).
Operating,
40 to 125°F (5 to 53°C).
Humidity:
95% non-condensing.
Shipping Weight:
0.4 lbs (170 g).
Location:
NEMA Type 1.
a On T20X-FP (freeze protection) models a relay will provide power to a valve or relay if the thermostat fails.
Table-1 Model Chart.
Model
Control Outputs
Fan
Control
System
Switch
Changeover
Mechanical Contact
B & O
Terminals
T201
Heating Only
None
Heat/Off
None
No
No
T201-FP
a
Heating Only
None
Heat/Off
None
Yes
No
T204
Cooling Only
On/Auto
Cool/Off
None
No
No
T205
Cooling & Heating
On/Auto
Cool/Off/Heat
Manual
No
No
T205-FP
a
Cooling & Heating
On/Auto
Cool/Off/Heat
Manual
Yes
No
T207
Cooling & Heating
On/Auto
Cool/Off/Heat
Manual
No
Yes
T207-FP
a
Cooling & Heating
On/Auto
Cool/Off/Heat
Manual
Yes
Yes