background image

9

VIEGA      1-800-976-9819 

PI-16015-03/09

Installing the outdoor sensor

The Outdoor Sensor includes a 

 

10k

Ω 

thermistor that provides an 

accurate measurement of the  
outdoor temperature. The sensor  

is protected by a white U.V. resistant 

plastic enclosure.

Remove the screw and pull the front 
cover off the sensor enclosure.

The Outdoor Sensor can either be 

mounted directly onto a wall or a 

2" x 4" electrical box. When the 
sensor is wall mounted, the wiring 
should enter through the back or 
bottom of the enclosure. Do not 

mount the sensor with the conduit 
knockout facing upward as rain  
could enter the enclosure and 
damage the sensor.

In order to prevent heat transmitted 
through the wall from affecting the 

sensor reading, it may be necessary 
to install an insulating barrier behind 

the enclosure.

The Outdoor Sensor should be 
mounted on a wall that best 

represents the heat load on the 

building (a northern wall for most 
buildings, and a southern facing wall 
for buildings with large south facing 

glass areas). The sensor should not 

be exposed to heat sources such as 

ventilation or window openings.

The Outdoor Sensor should be 
installed at an elevation above the 

ground that will prevent accidental 

damage or tampering, and where it 
will not be covered by drifting snow 

during the winter.

Connect 18 AWG or similar wire to 

the two terminals provided in the 
enclosure and run the wires from 
the sensor to the control. Do not 
run the wires parallel to telephone 

or power cables. If the sensor 

wires are located in an area with 
strong sources of electromagnetic 

interference (EMI), shielded cable or 
twisted pair should be used or the 
wires can be run in a grounded metal 
conduit. If using shielded cable, the 
shield wire should be connected 
to the COM sensor terminal on the 

control and not to earth ground.

Replace the front cover of the 
sensor enclosure.

When more than one Basic Heating 
Control is used on a project, the 
Outdoor Sensors can be combined 
into one enclosure by adding the 
Multiple Outdoor Sensor module 
(stock code 16020).  This mounts 

 

in the Outdoor Sensor enclosure 

 

and allows up to four controls to  
have outdoor sensors within  
one enclosure.

Installing the supply sensor

Note: This sensor is designed to 
mount on a pipe or in a temperature 
immersion well.

The Supply Sensor can be strapped 

directly to the pipe using a plastic 

cable tie. Insulation should be 

 

placed around the sensor to reduce 
the effect of air currents on the  
sensor measurement.

  

The Supply Sensor should be placed 

downstream of a pump or after 

an elbow or similar fitting. This is 

especially important if large diameter 

pipes are used, as the thermal 
stratification within the pipe can 

result in erroneous sensor readings. 

Proper sensor location requires that 

the fluid is thoroughly mixed within 

the pipe before it reaches the sensor. 
When using the Supply Sensor with 
a Viega Mixing or Injection Station, 

insert the sensor into the immersion 

well on the elbow below the 

circulator pump.  

Connect 18 AWG or similar wire 

to the two wires of the sensor 
and then to the control. Do not 
run the wires parallel to telephone 

or power cables.  If the sensor 

wires are located in an area with 
strong sources of electromagnetic 

interference (EMI), shielded cable or 
twisted pair should be used or the 
wires can be run in a grounded metal 
conduit. If using shielded cable, the 
shield wire should be connected 
to the COM sensor terminal on the 

control and not to earth ground.

InstALLAtIon - CHAPtER 5

Summary of Contents for Basic Heating Control

Page 1: ...Radiant Basic Heating Control Installation Manual March 2009...

Page 2: ...he supply water temperature The control has a Liquid Crystal Display LCD to view system status and operating information Additional functions include User comfort adjustment to increase or decrease bu...

Page 3: ...use the LCD display Control Sections 3 and 4 which discusses how the mixing device and boiler are controlled Installation Section 5 which details the mounting and connection process for the control a...

Page 4: ...in operation Burner Displays when the boiler relay is turned on F C Displays the units of measurement that all of the temperatures are to be displayed in the control Pointer Displays the actuator oper...

Page 5: ...d 9 The Basic Heating Control pulses the actuator motor open or closed to maintain the correct mixed supply water temperature at the supply sensor The valve that the actuator is connected to can be ei...

Page 6: ...r where the building is located This temperature is used when performing the heat loss calculations for the building If a cold outdoor design temperature is selected the mixing supply temperature rise...

Page 7: ...ion of the mixing valve exceeds 30 The boiler contact remains closed until the position of the mixing valve reduces below 15 This setting would normally be chosen for low mass boilers copper fin tube...

Page 8: ...n wiring hardware and conduit fittings Before removing the knockouts check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sec...

Page 9: ...s can be run in a grounded metal conduit If using shielded cable the shield wire should be connected to the COM sensor terminal on the control and not to earth ground Replace the front cover of the se...

Page 10: ...ircuit to the neutral N terminal 4 Valve Actuator Terminals 7 8 and 9 are powered with 24 VAC from the control There is no need to provide a separate 24 VAC power source for the valve actuator R Opn 7...

Page 11: ...o be tested and the readings compared Test the sensors according to the instructions on page 15 Test the Power Supply Make sure exposed wires and bare terminals are not in contact with other wires or...

Page 12: ...iring until the boiler pump is running If the boiler operates properly disconnect the power and remove the jumper Connecting the Control Make sure all power to the devices and terminal blocks is off a...

Page 13: ...n the User Interface see Display Settings below Boiler Enable 30 Boiler Enable 10 The position of this switch determines at which valve position the control will close the Boiler contact under normal...

Page 14: ...e 16108 on the Injection Station to protect control in case of main control failure or removal Set higher than MIX DSGN and account for the heat loss of distribution piping WWSD Warm Weather Shut Down...

Page 15: ...1k 1000 is required to measure the sensor resistance In addition to this the actual temperature must be measured with a good quality digital thermometer If a thermometer is not available a second sen...

Page 16: ...which devices should be operating as indicated by the LCD This information is an essential step if additional assistance is required to diagnose the problem Isolate the problem between the control and...

Page 17: ...control will operate the mixing valve at a fixed output Locate the problem as described in Section 5 7 To clear the error message from the control after the sensor has been repaired press the Item but...

Page 18: ...18 VIEGA 1 800 976 9819 PI 16015 03 09 MECHANICAL AND ELECTRICAL DIAGRAMS CHAPTER 7 Pump Pump Pump Pump...

Page 19: ...03 09 MECHANICAL AND ELECTRICAL DIAGRAMS CHAPTER 7 Three Position Actuator White wire common green wire open brown wire close Mixing Valve Actuator Blue wire common brown wire clockwise rotation black...

Page 20: ...Dimensions 6 5 8 H x 7 9 16 W x 2 13 16 D 170 x 193 x 72 mm Approvals CSA C US meets ICES FCC regulations for EMI RFI Ambient Conditions Indoor use only 32 to 102 F 0 to 39 C 90 RH non condensing Powe...

Page 21: ...21 VIEGA 1 800 976 9819 PI 16015 03 09 NOTES...

Page 22: ...22 VIEGA 1 800 976 9819 PI 16015 03 09 NOTES...

Page 23: ...23 VIEGA 1 800 976 9819 PI 16015 03 09 NOTES...

Page 24: ...industry Viega 301 N Main Wichita KS 67202 Phone 1 877 843 4262 1 800 976 9819 Fax 1 800 976 9817 www viega com PI IM 16016 03 09 ProPress System Flameless copper press technology ProPress System Fla...

Page 25: ...trol of Viega Mixing Stations Enhanced Mixing Stations and diverting valves The actuator is used in electronic temperature control systems which use hot and or cold water as the controlled medium in r...

Page 26: ...tion of a screw spindle which is driven in both directions by a synchronous motor through a set of gears A magnetic coupling limits the torque of the gear assembly and the driving force of the actuato...

Page 27: ...optional circulator activation function and built in transformer Features LED indicator lights 4 or 6 Zone Control options Simplified wiring Built in transformer Specifications Control Input Control...

Page 28: ...minal of the Zone Control Connect a jumper from the R1 terminal to 3 R2 terminal of the Zone Control See diagram to right Priority Operation Switching the DIP switch to Priority ON will cause all othe...

Page 29: ...field selectable differential The cool output differential is fixed at 2F degrees The setpoint is displayed and changed by pressing one of the setpoint buttons up or down Installation is simplified b...

Page 30: ...25 F 5 to 53 C Humidity 95 non condensing Shipping Weight 0 4 lbs 170 g Location NEMA Type 1 a On T20X FP freeze protection models a relay will provide power to a valve or relay if the thermostat fail...

Page 31: ...functional in heat only models Table 2 Field Selectable Jumper Options Feature Jumpered Not Jumpered 1 Display Celsius Fahrenheit 2 Heating operation differential 2 degrees 1 degree 3 Heat control No...

Page 32: ...0 VAC FAN RELAY COOLING RELAY RC Y G Optional 250 Ohm 5 watt resistor is needed only if power drops below 75 milliamps 1 1 1 Figure 3 Typical T204 Wiring to Cooling System With Single Transformer 24 V...

Page 33: ...G TRANSFORMER 120 VAC FAN RELAY COOLING RELAY RC RH Y W G HEATING RELAY 1 1 1 If one of the secondary sides of both transformers are grounded grounded sides must be connected together FACTORY INSTALLE...

Page 34: ...nd used in accordance with the instructions Even when instructions are fol lowed there is no guarantee that interference will not occur in a particular installation If this equipment causes harmful in...

Page 35: ...COOL OFF system switch and a FAN ON AUTO fan switch Applications include direct expansion cooling only systems Refer to Figure 3 T205 The T205 models are heat cool models with manual changeover The u...

Page 36: ...is below 75 milliamps install a 250 ohm 5 watt resistor in parallel across the switched load Recheck for 75 milliamps The T200 thermostats must have 75 milliamps to function properly 4 Verify system H...

Page 37: ...owerhead with the white cap Three indicator windows allow the position of the valve to be verified valve is open when red bar is visible in window Compact design provides additional clearance for inst...

Reviews: