General Operation
11 of 36
IM-HC 561174 1120 Basic Heating Control
The MIX DSGN temperature is the supply water temperature required
to heat the mixing zones when the outdoor air is as cold as the OUTDR
DSGN temperature.
3.6.5 Room (Room)
The ROOM is the desired room temperature for the mixing zones and
it provides a parallel shift of the Heating Curve. The room temperature
desired by the occupants is often different from the design indoor
temperature (MIX INDR). If the room temperature is not correct, adjusting
the ROOM setting increases or decreases the amount of heat available to
the building.
3.6.6 Mix Design (MIX DSGN)
3.7 Temperature Control Advanced Information
3.7.1 Mixing Indoor (MIX INDR)
The MIX INDR is the room temperature used in the original heat loss
calculations for the building. This setting establishes the beginning of the
Heating Curve for the mixing zones.
3.7.2 Mixing Maximum (MIX MAX)
The MIX MAX sets the highest water temperature that the control is
allowed to calculate as the MIX TARGET temperature. If the control does
target the MIX MAX setting, and the MIX temperature is near the MIX
MAX, the MAX segment will be displayed in the LCD while either the MIX
TARGET temperature or the MIX temperature is being viewed.
3.7.3 Warm Weather Shut Down (WWSD)
When the outdoor air temperature rises above the WWSD setting, the Basic
Heating Control turns on the WWSD segment in the display. When the
control is in Warm Weather Shut Down, the control does not operate the
heating system (except for exercising - see "3.4.4 Exercising" on page 9).