4.6 Adjust Menu Display Settings
To make an adjustment to a setting in the control, press and hold
simultaneously for 1 second, the Item, and buttons. The display will
then show the word ADJUST in the top right corner. Then select the
desired item using the Item button. Finally, use the and/or button to
make the adjustment. See sections "3.6 Temperature Control Installer
Information" on page 10 and "3.7 Temperature Control Advanced
Information" on page 11 for further discussion on these items and their
effect on control operation.
The desired room temperature.
Range: 35° F to 100° F
The design outdoor temperature used for calculating heat-loss. Obtained
from the Design Outdoor Temperature Chart or Viega’s Radiant Wizard*.
Range: -60° F to 32° F
The design supply water temperature obtained from the Supply Water
Temperature / BTU Output Chart, or Viega’s Radiant Wizard.
Range: 70° F to 220° F
The design indoor air temperature used in the heat loss calculation*
for the heating system (only visible with the Advanced/Installer DIP
switch set to Advanced). Should be equal to “ROOM,” the desired room
temperature.
Range: 35° F to 150° F
* See corresponding installation manuals, i.e., Concrete System, Climate Panel, or
Climate Trak for appropriate charts.
4.6.1 ROOM
4.6.2 OUTDR DSGN
4.6.3 MIX DSGN
4.6.4 MIX INDR