Troubleshooting
30 of 36
IM-HC 561174 1120 Basic Heating Control
5.3 Error Messages
The control was unable to read a piece of information from its EEPROM.
This error can be caused by a noisy power source. The control will load
the factory defaults and stop operation until the settings are verified.
The control is no longer able to read the Outdoor sensor due to a short
circuit. In this case the control assumes an outdoor temperature of
32° F (0° C) and continues operation. Locate the problem as described in
Section 5.7. To clear the error message from the control after the sensor
has been repaired, press the Item button.
The control is no longer able to read the Outdoor sensor due to an open
circuit. In this case the control assumes an outdoor temperature of
32° F (0° C) and continues operation. Locate the problem as described in
Section 5.7. To clear the error message from the control after the sensor
has been repaired, press the Item button.
The control is no longer able to read the Mixing Supply sensor due to
a short circuit. In this case the control will operate the mixing valve at a
fixed output. Locate the problem as described in Section 5.7. To clear the
error message from the control after the sensor has been repaired, press
the Item button.
5.3.1 E01
5.3.2 Shr (OUTDR
5.3.3 OPn (OUTDR)
5.3.4 Shr (MIX