Installation
16 of 36
IM-HC 561174 1120 Basic Heating Control
4.1.3 Installing the Outdoor Sensor
The Outdoor Sensor includes a 10kΩ thermistor that provides an accurate
measurement of the outdoor temperature. The sensor is protected by a
white U.V. resistant plastic enclosure.
Remove the screw and pull the front cover off the sensor enclosure.
The Outdoor Sensor can either be mounted directly onto a wall or a
2" x 4" electrical box. When the sensor is wall mounted, the wiring should
enter through the back or bottom of the enclosure. Do not mount the
sensor with the conduit knockout facing upward as rain could enter the
enclosure and damage the sensor.
In order to prevent heat transmitted through the wall from affecting the
sensor reading, it may be necessary to install an insulating barrier behind
the enclosure.
The Outdoor Sensor should be mounted on a wall that best represents
the heat load on the building (a northern wall for most buildings, and a
southern facing wall for buildings with large south facing glass areas).
The sensor should not be exposed to heat sources such as ventilation or
window openings.
The Outdoor Sensor should be installed at an elevation above the ground
that will prevent accidental damage or tampering, and where it will not be
covered by drifting snow during the winter.
Connect 18 AWG or similar wire to the two terminals provided in the
enclosure and run the wires from the sensor to the control. Do not run
the wires parallel to telephone or power cables. If the sensor wires are
located in an area with strong sources of electromagnetic interference
(EMI), shielded cable or twisted pair should be used or the wires can be
run in a grounded metal conduit. If using shielded cable, the shield wire
should be connected to the COM sensor terminal on the control and not
to earth ground.
Replace the front cover of the sensor enclosure.
When more than one Basic Heating Control is used on a project, the
Outdoor Sensors can be combined into one enclosure by adding the
Multiple Outdoor Sensor module (part number 16020). This mounts in the
Outdoor Sensor enclosure and allows up to four controls to have outdoor
sensors within one enclosure.
Multiple Outdoor Sensor
module mounting location
Wires from
outdoor sensor
to control
terminals
(Com Sen -
Out Sen)
Sensor is built
into the
enclosure