Installation
25 of 36
IM-HC 561174 1120 Basic Heating Control
The maximum supply temperature for the mixing system (only visible with
the Advanced/Installer DIP switch set to Advanced). This setting should
not be relied upon for a safety high limit. Set higher than “MIX DSGN”
and account for the heat loss of distribution piping.
Range: 80° F to 210° F or OFF
Warm Weather Shut Down; the design outdoor air temperature at
which the control only operates in exercising mode (only visible with the
Advanced/Installer DIP switch set to Advanced).
Range: 35° F to 100° F or OFF
The units of measure that all of the temperatures are to be displayed in
the control; either °F or °C.
4.6.5 MIX MAX
4.6.6 WWSD
4.6.7 UNITS