background image

VIEGA • 

Viega... The global leader in plumbing and heating systems.

301 N. Main, Floor 9 • Wichita, KS 67202 • Ph: 877-Viega-NA • Fax: 800-976-9817 • E-Mail: service@viega.com • www.viega.com

Product Instructions

Basic Digital Snow Melt Control II

PI-PR-17023 05/08

2 of 5

Installation

The components of the Basic Digital 
Snow Melt Control II

Snow Detector (17002)
Digital Setpoint Control II 
     with watertight sensor (17029)
Timer Switch (17013) 
Timer Face Plate (17014)
Watertight Sensor (17031)

The snow detector should be placed in 
a location where it will not be covered 
with drifting snow. Install a secure 1/2” 
rigid conduit to show a clearance above 
ground level of 2 to 3 feet minimum 
(depending upon annual snowfall). The 
snow detector may also be located on 
an exterior wall with full exposure to 
snow  and  ice  (no  overhang).  The  snow        
detector does not have to be located 
near the snow melting area, but should 
have full exposure to snow and ice 
(away from trees, roof overhangs, etc...).

For proper control, the sensor for the  
setpoint control must be located within 
the snow melting slab, and should be 
placed midway between rows of 
tubing.  The  sensor  should  be  placed  in         
conduit which is cast into the slab, so 
that replacement is possible. The sensor 
is extendable up to 100'.

Install the timer in a 3” deep electrical 
wall box with “TOP” (indicated on front 
cover) in proper position. Fasten cover 
to outlet box using two screws provided. 
Place calibrated wall plate on timer unit 
and fasten with nut provided. Push knob 
onto timer shaft. If knob is not centered 
on “0”, either the plate or the timer can 
be rotated slightly.

Typical Snow Melt Installation

(showing additional equipment)

Typical Snow Melting Cross-Section