Troubleshooting

If the snowmelting system is not operating correctly, i rst 
check that all electrical connections have been made 
properly. Check for power to all components 
(120V and 24V). 

If the snow detector does not activate the system during 
snowfall, turn on the timer switch. If this activates the 
system, replace the snow detector.  

If neither the timer or snow detector turns the system on, 
check the setpoint control coni guration.

If the coni guration is correct disconnect the slab sensor 
and check its resistance. Replace the sensor if its 
resistance value does not match the temperature in the 
accompanying chart to the right.  

 Temp °F

 Temp °C

 Resistance 

Ohms

-40

-40.0

851

-30

-34.4

872

-20

-28.8

893

-10

-23.3

914

0

-17.7

935

10

-12.2

956

20

-6.6

977

30

-1.1

998

40

4.4

1019

50

10.0

1040

60

15.5

1061

70

21.1

1082

80

26.6

1103

90

32.2

1124

100

37.7

1145

110

43.3

1166

120

48.8

1187

130

54.4

1208

140

60.0

1229

150

65.5

1250

160

71.1

1271

170

76.6

1292

180

82.2

1313

190

87.7

1334

200

93.3

1355

210

98.8

1376

220

104.4

1397

230

110.0

1418

240

115.5

1439

250

121.1

1460

Reviews: