10
Setting ranges (variable):
Vitovent 300 for max. air flow
rate
m
3
/h
180
300
400
Reduced ventilation
m
3
/h
50 to 170
50 to 290
50 to 390
Standard ventilation
m
3
/h
50 to 175
50 to 295
50 to 395
Higher ventilation
m
3
/h
50 to 180
50 to 300
50 to 400
Note
■ The actual air flow rates that the
Vitovent can achieve are subject to the
pressure drop of the duct system and
that of the filters (filter class).
■ The speed of both fans is automati-
cally adapted to maintain the selected
air flow rate irrespective of the level of
filter contamination.
Duct system (flat) metal: Pre-selecting the supply/extract air
apertures
You will need the following design
details:
■ Pressure drop for the section
■ Air flow rates for the section
These details enable the determination
and pre-selection of the required aper-
ture sizes for the supply air and extract
air apertures using the relevant dia-
grams.
Supply air valve for setting into a wall (DN 100)
20
Ø 99
Ø 143
Max. flow rate: 30 m
3
/h
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5608 999 GB