41
!
Please note
Incorrect adjustments can result
in interruption of operations.
Settings must only be made/
changed by a qualified contrac-
tor.
Incorrect operation by system
users will invalidate our war-
ranty.
Setting parameters:
1.
Set the rotary program selector to
"MENU"
.
2.
xw
for
"Service"
.
3.
d
to confirm.
4.
xw
for
"Parameter"
.
5.
d
to confirm; the first parame-
ter "00" is displayed; the set
value flashes.
6.
xw
to change the value
Note
Only flashing values can be
changed.
Non-flashing values are
operating data.
or
d
for the next parameter.
7.
d
to confirm a selected value.
8.
"
ESC
" to exit the menu.
Note
"Service" will be shown again if no key
if pressed during the adjustment proce-
dure for more than 1 min.
Parameter overview
Param
eters
Description
Delivered
condition
Setting range
00
Air flow rate for
reduced ventilation in
m
3
/h.
Setting: At least 10 m
3
/h lower than the
setting for standard ventilation.
For the Vitovent with max. air flow rate
180 m
3
/h:
75 50 to 170 m
3
/h
For the Vitovent with max. air flow rate
300 m
3
/h:
100 50 to 290 m
3
/h
For the Vitovent with max. air flow rate
400 m
3
/h:
100 50 to 390 m
3
/h
Remote control
Setting parameters
5608 999 GB