42
Param
eters
Description
Delivered
condition
Setting range
01
Air flow rate for
standard ventilation in
m
3
/h.
Setting:
■ At least 10 m
3
/h higher than the setting
for reduced ventilation.
■ At least 5 m
3
/h lower than the setting
for higher ventilation.
For the Vitovent with max. air flow rate
180 m
3
/h:
100 50 to 175 m
3
/h
For the Vitovent with max. air flow rate
300 m
3
/h:
150 50 to 295 m
3
/h
For the Vitovent with max. air flow rate
400 m
3
/h:
200 50-395 m
3
/h
02
Air flow rate for
higher ventilation in
m
3
/h.
Setting: At least 5 m
3
/h higher than the
setting for standard ventilation.
For the Vitovent with max. air flow rate
180 m
3
/h:
150 50 to 180 m
3
/h
For the Vitovent with max. air flow rate
300 m
3
/h:
225 50 to 300 m
3
/h
For the Vitovent with max. air flow rate
400 m
3
/h:
300 50 to 400 m
3
/h
03
Set outdoor air temperature for closing
the bypass in °C (only for Vitovent 300
for max. air flow rate 300 m
3
/h or
400 m
3
/h)
The bypass is closed (active heat recov-
ery) if
one
of the following conditions
applies:
■ Outdoor air temperature
>
Extract air
temperature
■ Outdoor air temperature
<
Set outdoor
air temperature (
"03"
)
■ Extract air temperature
<
Set extract
air temperature (
"04"
)
10 5 to 20 °C
Remote control
Setting parameters
(cont.)