46
Calling up operating data
1.
Set the rotary program selector to
"MENU"
.
2.
xw
for
"Service"
.
3.
d
to confirm.
4.
xw
for
"Parameter"
.
5.
d
to confirm; the first parame-
ter "00" is displayed; the set
value flashes.
6.
xw
to change the value.
Note
Only flashing values can be
changed.
Non-flashing values are
operating data.
or
d
for the next parameter.
7.
d
to confirm a selected value.
8.
"
ESC
" to exit the menu.
The default display will be shown again
if no key is pressed for more than
5 min.
The following operating data can be scanned:
Param
eters
Meaning
Value range
12
Appliance type:
Vitovent for a maximum air flow
rate
Note
The actual value can, subject to sys-
tem, deviate from the values
shown.
180 m
3
/h, 300 m
3
/h or 400 m
3
/h
13
Air flow rate, actual value
0 to 400 m
3
/h
Troubleshooting
Diagnosis at the remote control
5608 999 GB