57
Domestic ventilation system with Vitovent
System:
Heating contractor:
Contact:
Date:
Air flow rates for standard operation with 0.5 air change
Appliance settings
=......................m³/h
..................m³/h
Total flow rate
Supply air
Extract air
..................m³/h
..................W
Power consumption
Supply and extract air apertures
Supply air
Living room
Living room Dining room
Bedroom
Study
Child's room 1
Child's room 2
Design flow rate [m³/h]
Supply air/ extract air valve
Preset aperture width
First measurement (average)
Air speed [m/s]
Air flow rate [m³/h]
Readjusted aperture width
Second measurement (average)
Air speed [m/s]
Air flow rate [m³/h]
Supply air total
Extract air
Kitchen
Bathroom
Guest WC
Utility room
Extract air total
Sample person
160
163
152
46
25
25 25
30
30
25
160
60
45
20
25
160
Wall installation
Wall installation
Wall installation
Ceiling installat.
Ceiling installat.
Ceiling installat.
5.5
5.5
5.5
6
6
5
3.5
3.5
3.5
3.0
4.0
2.5
22
22
22
24
36
20
146
+1
+1
+1
+2
-1
+1
3.3
3.3
3.3
3.2
3.8
2.6
25
25
25
36
30
22
163
Extract air valve:
Extract air valve
Extract air valve
Extract air valve
+12
+9
+10
-8
6.3
5.2
5.0
6.0
50
38
15
20
137
-
+4
+3
+7
4.0
4.4
4.2
3.2
70
42
20
20
152
Commissioning/service reports
Commissioning report example
5608 999 GB