58
Vitovent 300 for max. air flow rate
m
3
/h
180
300
400
Air flow rate setting range (varia-
ble)
Reduced ventilation
m
3
/h
50 - 170
50 - 290
50 - 390
Standard ventilation
m
3
/h
50 - 175
50 - 295
50 - 395
Higher ventilation
m
3
/h
50 - 180
50 - 300
50 - 400
Max. air flow rate
m
3
/h
180
300
400
External pressure drop
at max. air
flow rate
Pa
200
100
100
Factory-setting, air flow rate
Reduced ventilation
m
3
/h
75
100
100
Normal ventilation
m
3
/h
100
150
200
Higher ventilation
m
3
/h
150
225
300
Casing
Material
Colour
Sound and thermal insulation
Sheet steel
White
EPP/EPS plastic mouldings
Dimensions
excluding connectors
Length (depth)
mm
310
436
436
Width
mm
560
675
675
Height
mm
600
747
747
Weight
kg
25
31
32
DC radial fan
With constant flow rate control, inlet
on one side only, with forward curved
impeller vanes
Num-
ber
2
Filter
to DIN EN 779
Supply air
Filter
class
G3 (as delivered condition)
F7 (accessory)
Extract air
Filter
class
G3 (as delivered condition)
G4 (accessory)
Countercurrent heat exchanger
Heat recovery level
%
up to 92
up to 91
up to 91
Material
PETG plastic
Rated voltage
230 V/50 Hz
Max. power consumption
W
132
174
300
Specification
Specification
5608 999 GB