136
The duration of the changeover is set via parameter F2
in the
"Heating circuit"
group.
Effect of external blocking function on the pumps
The effect on the internal circulation pump is selected
via parameter 3E in the
"General"
group.
The effect on the relevant heating circuit pump is
selected via parameter d6 in the
"Heating circuit"
group.
The effect on a circulation pump for cylinder heating is
selected via parameter 5E in the
"DHW"
group.
Effect of the external demand function on the
pumps
The effect on the internal circulation pump is selected
via parameter 3F in the
"General"
group.
The effect on the relevant heating circuit pump is
selected via parameter d7 in the
"Heating circuit"
group.
The effect on a circulation pump for cylinder heating is
selected via parameter 5F in the
"DHW"
group.
DHW circulation pump runtime for brief operation
The DHW circulation pump is started by closing the
contact at DE1, DE2 or DE3 by means of a pushbut-
ton. The runtime is set via parameter "3d" in
the
"General"
group.
Analogue input 0
–
10 V
The 0
–
10 V hook-up provides an additional set boiler
water temperature:
0
–
1 V is taken as "no specification for set boiler
water temperature".
1 V
≙
Set value 10 °C
10 V
≙
Set value 100 °C
Ensure DC separation between the earth conductor
and the negative pole of the on-site power source.
Output
aBJ
The following functions can be connected to output
aBJ
:
■
Feed pump to substation
or
■
DHW circulation pump
or
■
Fault message facility
Information on the feed pump
Function only possible in conjunction with a heating
circuit control unit connected via LON.
Information on DHW circulation pumps
Connect DHW circulation pumps with standalone func-
tions directly to the 230 V
∼
supply.
Function assignment
The function of output
aBJ
is selected via parameter
"36" in the
"General"
group at the boiler control unit.
Control functions
External operating program changeover
The "External operating program changeover" function
is implemented via the EA1 extension. There are 3
inputs available at the EA1 extension (DE1 to DE3).
The function is selected via the following parameters in
the
"General"
group:
Operating program changeover
Parameter
Input DE1
3A:1
Input DE2
3b:1
Input DE3
3C:1
Select the operating program changeover function for
the respective heating circuit via parameter d8 in the
"Heating circuit"
group at the boiler control unit:
Operating program changeover
Parameter
Changeover via input DE1
d8:1
Changeover via input DE2
d8:2
Changeover via input DE3
d8:3
Function description
External extensions (accessories)
(cont.)
5789 302 GB
Functions