141
Example using the settings in the delivered condition
10
0
20
30
30
40
50
60
6
7
8
9
Boiler
water
temperature/
set flow temperature
in
°C
Time
A
B
C
D
Fig. 87
A
Start of operation with standard room temperature
B
Set boiler water or flow temperature in accordance
with the selected heating curve
C
Set boiler water temperature or set flow tempera-
ture in accordance with parameter FA:
50 °C + 20 % = 60 °C
D
Duration of operation with higher set boiler water
temperature or set flow temperature in accordance
with parameter Fb:
60 min
Assigning heating circuits to the remote control
The assignment of heating circuits must be configured
during remote control commissioning.
Remote control affects the following heating circuit:
Configuration
Vitotrol 200-A
Vitotrol 300-A
Vitotrol 200-RF
Vitotrol 300-RF
Heating circuit without mixer A1
H 1
Heating circuit 1
Heating circuit with mixer M2
H 2
Heating circuit 2
Heating circuit with mixer M3
H 3
Heating circuit 3
Note
One heating circuit can be assigned to the Vitotrol 200-
A and 200-RF.
Up to 3 heating circuits can be assigned to the Vitotrol
300-A and 300-RF.
A maximum of 2 hardwired remote control units
or
3
wireless remote controls may be connected to the con-
trol unit.
If the assignment of a heating circuit is later cancelled,
reset parameter A0 in the
"Heating circuit"
group for
this heating circuit to 0 (fault message bC, bd, bE).
Function description
Control functions
(cont.)
5789 302 GB