If a Vitocom 100, type GSM (accessories) has been
connected to the heat source, enter the PIN code on
the Vitotronic control unit.
After entry, you may have to wait 10 to 15 s.
Tap the following buttons:
1. "Menu"
2. "Service"
3.
Enter
"viservice"
password.
4. "Service functions"
.
5. "Vitocom 100 GSM SIM PIN entry"
Further information:
"Vitocom 100" installation and service instruc-
tions
Hydronic balancing
When carrying out hydronic balancing using the
"Hydronic balancing service case with Vitosoft 300",
"Hydraulic balancing ENABLED"
appears on the
display.
While the function is enabled, it is not possible to oper-
ate the boiler via the Vitotronic control unit.
The boiler is unavailable for heating operation or other
functions during hydronic balancing. The burner does
not start.
Electronic combustion control unit
The electronic combustion controller utilises the physi-
cal correlation between the level of the ionisation cur-
rent and the air ratio
λ
. The maximum ionisation cur-
rent is achieved at an air ratio of 1 for all gas qualities.
The ionisation signal is evaluated by the combustion
controller and the air ratio is adjusted to a value
between
λ
=1.24 and 1.44. This range provides for an
optimum combustion quality. Thereafter, the electronic
gas valve regulates the required gas volume subject to
the prevailing gas quality.
To check the combustion quality, the CO
2
content or
the O
2
content of the flue gas is measured. The pre-
vailing air ratio is determined with the measured val-
ues. The relationship between the CO
2
or O
2
content
and air ratio
λ
is illustrated in the following table.
Air ratio
λ–
CO
2
/O
2
content
Air ratio
λ
O
2
content (%) CO
2
content (%) for
natural gas E
CO
2
content (%) for
natural gas LL
CO
2
content (%) for
LPG P
1.20
3.8
9.6
9.2
11.3
1.24
4.4
9.2
9.1
10.9
1.27
4.9
9.0
8.9
10.6
1.30
5.3
8.7
8.6
10.3
1.34
5.7
8.5
8.4
10.0
1.37
6.1
8.3
8.2
9.8
1.40
6.5
8.1
8.0
9.6
1.44
6.9
7.8
7.7
9.3
1.48
7.3
7.6
7.5
9.0
Function description
Vitocom 100, type GSM: Entering PIN code via Vitotronic
5789 302 GB
Functions
Summary of Contents for B2TB
Page 6: ...6 15 Keyword index 152 Index Index cont 5789 302 GB ...
Page 117: ...117 Parts lists Hydraulics 5789 302 GB Components ...
Page 154: ...154 5789 302 GB ...
Page 155: ...155 5789 302 GB ...