46
B A
C
Fig. 35
1.
Remove cover
A
(two-part design up to 26 kW).
2.
Remove earth cable
B
from tab
C
.
3.
Connect tester (up to 5 mA) in series between tab
C
and earth cable
B
.
■
If the current measures > 0.3 mA the magnesium
anode is OK.
■
If the current measures < 0.3 mA or if there is no
current at all, inspect the magnesium anode visu-
ally (see page 47).
Draining the boiler on the DHW side
Fig. 36
1.
Connect the hose to the drain valve and route it
into a suitable container or drain outlet.
Note
Ensure adequate ventilation in the DHW pipework.
2.
Turn drain valve from lever position
A
(opera-
tional) to lever position
B
or
C
as required.
■
Lever position
B
: the DHW circuit in the appli-
ance
excluding
the DHW cylinder is drained via
the cold water connection.
■
Lever position
C
: the DHW circuit in the appli-
ance
and
DHW cylinder are drained via the hot
water connection. The cold water connection
remains filled.
Commissioning, inspection, maintenance
Checking the anode connection and anode earth…
(cont.)