54
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
Control unit is fault manager.
Parameter "79:1"
Control unit is not fault man-
ager.
Parameter "79:0"
Control unit is not fault man-
ager.
Parameter "79:0"
Device is fault man-
ager.
Control unit transmits the
time.
Parameter "7b:1"
Control unit receives the
time.
Set
parameter "81:3".
Control unit receives the
time.
Set
parameter "81:3".
Device receives the
time.
Control unit transmits outside
temperature.
Set
parameter "97:2".
Control unit receives outside
temperature.
Set
parameter "97:1".
Control unit receives outside
temperature.
Set
parameter "97:1".
—
Viessmann system number.
Parameter "98:1"
Viessmann system number.
Parameter "98:1"
Viessmann system number.
Parameter "98:1"
—
LON subscriber fault monitor-
ing.
Parameter "9C:20"
LON subscriber fault moni-
toring.
Parameter "9C:20"
LON subscriber fault moni-
toring.
Parameter "9C:20"
—
Carrying out a LON subscriber check
The subscriber check is used to test communication
with the system devices connected to the fault man-
ager.
Requirements:
■
The control unit must be enabled as
fault manager
(parameter "79:1" in the
"General"
group).
■
The LON subscriber number must be set in all con-
trol units.
■
The LON subscriber list in the fault manager must be
up to date.
Tap the following buttons:
1. "Menu"
2. "Service"
3.
Enter
"viservice"
password.
4. "Service functions"
5. "LON subscriber check"
The list of all connected LON subscribers appears.
6.
Select subscriber and confirm with
"OK"
.
The subscriber check for the selected subscriber is
initiated.
■
If the subscriber check was successful,
"Check OK"
is shown.
■
If the subscriber check was unsuccessful,
"Check
not OK"
is shown.
Note
To perform another subscriber check:
Create a new subscriber list with
"New list"
. The
subscriber list is updated.
Note
During the subscriber check, the display of the relevant
subscriber shows the subscriber no. and
"Wink"
for
approx. 1 min.
Calling up and resetting the "Service" display
Service indicator
It is possible to set threshold limits for a service using
either the commissioning assistant or by setting
parameters "21" and "23" in the
"Boiler"
group.
When these limit values are then reached, a service
message appears in the display.
Tap the following buttons:
1. "Confirm"
flashes in the footer.
2.
Note
After tapping the following will be displayed if
your heating system has several fault messages
simultaneously:
3. "Service, messages"
The service messages appear yellow in a list.
Commissioning, inspection, maintenance
Connecting the control unit to the LON
(cont.)
5789 302 GB