86
5.
Tap the system component that you wish to
change. A list containing the current settings and
the switching states appears.
Brief scan
In the brief scan, you can scan temperatures or call up
software versions and connected components, for
example.
Tap the following buttons:
1. "Menu"
2. "Service"
3.
Enter
"viservice"
password.
4. "Diagnosis"
5. "Brief scan"
Fig. 50
6. "Code"
An overview of the brief scan appears, with 14
rows and 6 fields.
Fig. 51
7.
/ for the required brief scan in line with the fol-
lowing table
Meaning of the relevant values in the individual rows and fields:
Row (brief
scan)
Field
1
2
3
4
5
6
1:
System scheme 01 to 10
Software version
Control unit
Software version
Programming unit
2:
0
0
Appliance version
Appliance ID CU-ID
3:
0
0
Number of KM-BUS subscrib-
ers
Software version solar control
module SM1
4:
Software version
Burner control unit
Type
Burner control unit
Burner control unit version
5:
Burner starts until next calibration
Escalation
stage, calibra-
tion
Software ver-
sion, AM1 ex-
tension
Software ver-
sion, EA1 exten-
sion
6:
0
0
0
Switching
state of flow
switch (only
for combi boil-
er)
0: OFF
1: Active
0
0
Diagnosis and service scans
Diagnosis
(cont.)
5789 302 GB