108
Parameter
Code
Delivered condi-
tion
Commis-
sioning
Enable compressor
5100
1
DHW
Set DHW temperature
6000
500 (
≙
50 °C)
Min. DHW temperature
6005
100 (
≙
10 °C)
Max. DHW temperature
6006
600 (
≙
60 °C)
Hysteresis DHW temperature heat pump 6007
70 (
≙
7 K)
Hysteresis DHW temperature booster
heater
6008
100 (
≙
10 K)
Start optimisation for DHW heating
6009
0
Stop optimisation for DHW heating
600A
0
Set DHW temperature 2
600C
600 (
≙
60 °C)
Temperature sensor at bottom of DHW
cylinder
600E
0
Enable booster heaters for DHW heating 6014
0
Enable electric heaters for DHW heating 6015
1
Priority DHW heating with combi cylin-
der
6016
0
Start attempts for DHW after high pres-
sure shutdown
6017
1
Operating mode cylinder primary pump
6020
Do not adjust
Electric booster heater
Enable instantaneous heating water
heater
7900
0
Enable instant. heating water heater for
central heating
7902
1
Max. output instantaneous heating water
heater
7907
3
Output for instant. heating water heater at
power-OFF
790A
0
Dual mode temp. instant. heating water
heater
790B
100 (
≙
10 °C)
Internal hydraulics
Heat pump for drying a building
7300
0
Time program for screed drying
7303
0
Set flow temperature, external demand
730C
500 (
≙
50 °C)
Operating mode primary pump
7320
Do not adjust
Operating mode secondary pump
7340
Do not adjust
Commissioning/service reports
Control parameters report
(cont.)
5601 574 GB
Summary of Contents for BWT 221.A06
Page 20: ...20 aCH 10 9 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 22: ...22 4x 18 21 4x 6x 20 2x 19 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 23: ...23 25 2x 24 4x 22 23 Installation sequence Siting the heat pump cont 5601 574 GB Installation ...
Page 28: ...28 4 1 3 2 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 71: ...71 Opening programming unit 2 2x 1 3 Troubleshooting Repairs cont 5601 574 GB Service ...
Page 122: ...122 5601 574 GB ...
Page 123: ...123 5601 574 GB ...