26
Assembly and sealing faces to note
A
1.
Install the heat pump module in
reverse order to that described on
page 24.
With the pipe outlets, ensure dia-
phragm grommets
A
are seated
correctly.
Seal diaphragm grommets
A
with
sealing tape if required.
2.
Fit the cylinder module in reverse
order to that described on page 18.
!
Please note
Make tight hydraulic connec-
tions between the heat pump
and cylinder modules.
Ensure mounting plate
C
is
seated correctly (see diagram
below).
!
Please note
To prevent the formation of
condensate and the exces-
sive development of noise,
seal shield
D
tightly (see dia-
gram below).
Note
The shield stands slightly proud when
closed on account of the sound insu-
lating mat.
!
Please note
Seal the appliance so it is
soundproof and diffusion-
proof.
Sealing tape on the side pan-
els must be in close contact
with sealing faces
B
on the
casing.
Installation sequence
Siting the heat pump
(cont.)
5601 574 GB
Summary of Contents for BWT 221.A06
Page 20: ...20 aCH 10 9 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 22: ...22 4x 18 21 4x 6x 20 2x 19 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 23: ...23 25 2x 24 4x 22 23 Installation sequence Siting the heat pump cont 5601 574 GB Installation ...
Page 28: ...28 4 1 3 2 Installation sequence Siting the heat pump cont 5601 574 GB ...
Page 71: ...71 Opening programming unit 2 2x 1 3 Troubleshooting Repairs cont 5601 574 GB Service ...