41
sK
Relay output, either:
■
Central fault message
■
Circulation pump for cylinder heating
■
External heating circuit pump
■
DHW circulation pump
Code 53
dG
Gas train
gD
Flue gas damper (accessories)
aVG
KM-BUS subscriber (accessories)
■
Vitotrol 200-A or 300-A remote control unit
■
Mixer extension kit
■
Solar control module, type SM1
■
EA1 extension
■
Wireless base station
■
AM1 extension
a¢Ö
Fan motor
0-10 V
A1
Main PCB
A3
Coding card
A4
ON/OFF switch
A5
Programming unit
A6
Connection adaptor with Optolink
A7
Connection adaptor
A8
LON communication module (accessories)
A9
Reset
A10 Connection extension
A11 Output extension
Specification
Rated heating output range
TF/TR = 50/30
kW
16 - 80 32 - 120 32 - 160 48 - 200 48 - 240 64 - 280
64 - 318
TF/TR = 80/60
kW
15 - 74 29 - 110 29 - 146 44 - 184 44 - 220 58 - 258
58 - 291
Rated heat input
kW
76
113
151
189
226
264
300
Product ID
CE-0085CR0391
Permiss. operating temper-
ature
°C
95
Permiss. flow temperature
(= safety temperature)
°C
110
Max. permiss. operating
pressure
bar
6
MPa
0.6
Min. permiss. operating
pressure
bar
0.5
MPa
0.05
Test pressure
bar
7.8
MPa
0.78
Boiler body dimensions
Length/handling dimension
*1
mm
660/450 780/570 780/570
900
900
1010
1010
Width
mm
680
680
680
680
680
680
680
Height
mm
1459
1459
1459
1459
1459
1459
1459
Overall dimensions without
boiler flue connection
Length g
mm
745
875
875
980
980
1090
1090
Width c
mm
750
750
750
750
750
750
750
Height a
mm
1500
1500
1500
1500
1500
1500
1500
Foundation dimensions
Length
mm
750
850
850
1000
1000
1100
1100
Width
mm
800
800
800
800
800
800
800
Height
mm
100
100
100
100
100
100
100
*1
With unassembled base rail
Connection and wiring diagram
(cont.)
5792 916 GB
Summary of Contents for CI1