100
Displayed
fault code
System characteris-
tics
Cause
Measures
dd
Control mode without
room influence
Lead break, room
temperature sen-
sor, heating circuit
1 (without mixer)
Check room temperature
sensor for heating circuit 1
and remote control set-
tings (see page 125)
dE
Control mode without
room influence
Lead break, room
temperature sen-
sor, heating circuit
2 (with mixer)
Check room temperature
sensor for heating circuit 2
and remote control set-
tings (see page 125)
dF
Control mode without
room influence
Lead break, room
temperature sen-
sor, heating circuit
3 (with mixer)
Check room temperature
sensor for heating circuit 3
and remote control set-
tings (see page 125)
E0
Control mode
Fault external LON
subscriber
Check connections and
LON subscribers
E1
Burner in a fault
state
Ionisation current
too high during cal-
ibration
Check gap between ioni-
sation electrode and
burner gauze assembly
(see page 21).
In open flue mode, pre-
vent very dusty conditions
for the combustion air.
Press reset button
R
E3
Burner in a fault
state
Heat transfer too
low during calibra-
tion.
Temperature lim-
iter caused shut-
down.
Ensure adequate heat
transfer.
Press reset button
R
E4
Burner blocked
Fault, supply volt-
age 24 V
Replace control unit
E5
Burner blocked
Fault, flame ampli-
fier
Replace control unit
Troubleshooting
Fault codes
(cont.)
5692 860 GB